11                Biogas Risk Assessment

11.1          Introduction

11.1.1      It is proposed that mud would be left in place at the west and east corners of the WDII reclamation within the Causeway Bay Typhoon Shelter.  The other areas of the Typhoon Shelter would be fully dredged.  The marine sediment may contain organic matter.  When marine sediments rich in organic matter are covered over by reclamation fill, anaerobic degradation of the organic matter in the sediments would generate biogas (methane) which could pose a potential risk to the overlying future landuse.  The issue of methane risk is not a requirement in the TM on EIA Process but warrants investigation, as required in the Study Brief.  The potential gas emission from the proposed reclamation within the Causeway Bay Typhoon Shelter is assessed in this section.

11.2          Assessment Methodology and Criteria

Field Sampling and Laboratory Analysis

11.2.1      Vibrocores MV17 and MV18 are located within the western and eastern corners of the Typhoon Shelter, respectively, in the areas where marine mud is proposed to be left in place (Figure 6.1). Total Organic Carbon (TOC) and Sediment Oxygen Demand (SOD) levels in the sediment samples collected from vibrocores MV17 and MV18 are used for the assessment of methane hazard.  The results are presented in Table 11.1.  It is noted that the extent of dredging may change subject to more detailed engineering evaluation.  Further analysis of sediment samples at other locations would be required should sediment be proposed to be left in-situ in areas additional to the western and eastern corners of the Causeway Bay Typhoon Shelter.

Table 11.1  Sample Locations and Levels of Total Organic Carbon and Sediment Oxygen Demand

Location

Sample Depth

(m)

Moisture

(% w/w)

TOC

(% dry wt)

SOD*

(mg/kg)

MV17

0 - 0.9

1.0 - 1.9

61.2

32.6

4.82

1.04

13351

2804

Mean

47

2.93

8078

MV18

0 – 0.9

46.6

1.57

9775

1 – 1.9

36.1

1.86

6901

Mean

41

1.72

8338

Note:       * A testing duration of 5 days and 20 days was used for the determination of SOD.  The test results for the 20-day SOD test are adopted as a higher value was obtained.  Sample weight = 1.5 g.

Background

11.2.2      Typically, landfill gas hazard assessment has been undertaken using guidance or standards based on the concentrations of gases (methane and carbon dioxide), rather than mass flow rates.  Such guidance usually recommends restrictions on development in areas where the gas concentration exceeds a stated proportion of the lower explosive limit (LEL) of methane, which is 5% (v/v).  Typical margins of safety are in the range of 1 - 20% of LEL (0.05 - 1% (v/v)).

11.2.3      Most of the guidance on this subject has been developed for application to sanitary landfill sites and much less has been written on the subject of standards or guidance for levels of methane arising from other sources, such as natural peat formations, marshland, rice paddies, coal measures and other organic deposits of anthropogenic origin, such as marine sediments.  In fact, methane arises naturally in many areas that have apparently been safely developed or redeveloped without any regard for gas protection measures.

Development of Guide Levels

11.2.4      There is no primary legislation in Hong Kong covering hazards to development caused by landfill gas, or methane gas generated from anthropogenic organic deposits.  The most relevant guidance is the guideline, “Landfill Gas Hazard Guidance Note” issued by the Environmental Protection Department (EPD).  The guidance note states that no works and no entry to the development site should be allowed and the personnel on-site should be evacuated if the methane concentration of the development site exceeds 1.0% (v/v).

11.2.5      Perhaps the best example of methane problems arising from anthropogenic organic deposits is that of the London Docklands.  During redevelopment of this area, where disused docks containing contaminated silts and sediments had been backfilled, methane concentrations of 20 - 30% were commonly found in monitoring boreholes([1]), but in the majority of cases emission velocities from a 50 mm diameter borehole were below 0.01 m s-1.  Carpenter therefore recommended that development should not take place where emission rates exceed 0.05 m s-1 in a 50 mm diameter borehole.  This is the same as a flux of 0.05 m3 m-2 s-1 or 4,320 m3 m-2 per day through a surface with a cross-sectional area equivalent to the cross-sectional area of the borehole (that is, p r2, where r is the radius of the borehole).  Reference is also made to Carpenter’s work in the ICRCL guidance on the development and after-use of landfill sites([2]).

11.2.6      The UK Department of the Environment Waste Management Paper on Landfill Completion([3]) recommends as a completion criterion that methane emission rates from monitoring boreholes should fall consistently below 0.015 m3 per hour.  The completion criterion must be met in order for monitoring to be discontinued and for the operator to surrender the licence that obliges him to maintain aftercare of the site.  It is generally taken as an indication that the site does not pose continuing threat to the environment.  For a borehole with a diameter of 100 mm (the minimum recommended in Waste Management Paper 26A) having a cross sectional area of 7,854 mm2, this is equivalent to 45.84 m3 m-2 per day.  For larger boreholes of up to 250 mm diameter, the equivalent rate would be 7.35 m3 m–2 per day.

11.2.7      The above derived values are not the equivalent of gas fluxes through a freely-venting surface.  For landfills in the UK in particular, the guidance assumes a capping layer of low permeability.  In these cases a borehole installed through the cap acts to release static gas pressure in the fill. As a result, the flow of gas from the borehole will represent the flux through a freely-venting surface of greater cross-sectional area than the borehole itself because gas will be drawn from the surrounding area to the borehole under the influence of the pressure gradient.  It is difficult to estimate the radius of influence of such boreholes.  In sanitary landfills, radii of influence of 25 m can be achieved under active pumping at pressures of 5 mbar.  Assuming a linear relationship and a static pressure of 0.5 mbar the radius of influence of the borehole would reduce to 2.5 m.  If the emission from the borehole is assumed to be equivalent to the flux over an area of radius 2.5 m, the resultant flux would range from 18.3 L m-2 per day (based on the recommendation of the Waste Management Paper No. 26A) to 432 L m-2 per day (based on Carpenter’s guidance level).

11.2.8      The UK Department of the Environment Waste Management Paper No. 26A on Landfill Completion also recommends a maximum acceptable rate of methane ingress into a building constructed on a disused landfill site.  This criterion was developed to determine when monitoring of landfill gas emissions at a restored landfill can be discontinued and when the site can be used for unrestricted development.  It is assumed that the most sensitive ‘at risk’ room or void has a height of 2.5 m and a very low rate of ventilation of 1 air change per week.  For WDII, it is considered more appropriate to adopt a height of 1 m to represent the void space (to allow for smaller void spaces such as utilities or services ducts) and a ventilation rate of 1 air change per day (this is in line with rates of natural ventilation for closed rooms).  The maximum safe rate of methane ingress was then defined as that at which it would take 1 day for the methane concentration to reach 1% (v/v).  This is 20% of the lower explosive limit (LEC) for methane and provides a safety factor of 5.  The corresponding daily maximum “safe” rate of methane gas emission per unit area is calculated to be 10 L m-2 per day([4]). 

11.2.9      The EPD’s guidance note on landfill gas hazard and the UK guidance values (that is, the UK completion criterion for landfills; the Carpenter’s guidance level and the “safe” gas emission rate), will be adopted as the assessment criteria (Table 11.2).

Table 11.2    Methane Hazard Assessment Criteria

EPD’s Guidance Note (% v/v)

UK Guidance Values  (L m-2 d-1)

1 (1)

18 (2) – 432 (3)

10 (4)

Notes:

(1)     Guideline value from Landfill Gas Hazard Guidance Note, EPD, HK.

(2)     UK Landfill Completion Criterion from Department of the Environment (1993), Landfill Completion. Waste Management Paper No. 26A, London: HMSO.

(3)     Carpenter’s guidance levels.

(4)     Maximum “safe” rate of gas emission derived for WDII, as based on Department of the Environment (1993), Landfill Completion.  Waste Management Paper No. 26A.  London: HMSO.

 

11.3          Calculation of Potential Gas Emissions

11.3.1      From Table 11.1, the calculated mean TOC level at vibrocore location MV17 is 2.93% on a dry weight basis and the calculated mean SOD level is 8,078 mg kg-1.  Based on an average moisture content of 47%, dry matter made up 53% of the sediment on average.  At vibrocore location MV18, the calculated mean TOC level is 1.72% on a dry weight basis and the calculated mean SOD level is 8,338 mg kg-1.  Based on an average moisture content of 41%, dry matter made up 59% of the sediment on average.

11.3.2      The potential methane gas emission was estimated based on the assumption that marine mud would be left in-situ at the WDII reclamation within the western and eastern corners of the Causeway Bay Typhoon Shelter.  The quantity of mud was estimated to be 42,422 m3  and 6,732 m3 at the western and eastern corners, respectively  :

 

Volume of mud left in-situ at western corner =          21,211 m2 x 2 m    =      42,422 m3

Volume of mud left in-situ at eastern corner  =          3,366 m2 x 2 m    =        6,732 m3

11.3.3      The average depth of sediment at the reclamation area of concern is approximately 4.5 m.  The hydraulic and water quality studies undertaken in 1989([5]) indicated that the siltation rate in the Victoria Harbour was around 50 mm per year.  This suggests that the age of sediment in the reclamation area at depths of 4.5 m below seabed would be around 90 years.  Other sediment and ecological studies([6],[7]) have demonstrated that the Redox Potential Discontinuity (RDP) depth (or the oxygenated surface layer) of marine sediment in the Victoria Harbour is generally limited to the top 10 cm.  Anaerobic degradation of the organic matter may occur in sediments that are below 10 cm from the seabed.  Based on the range of half-lives of 0.5 to 5 years, most of the readily degradable organic matter would have been anaerobically degraded and the current methane generation potential of this sediment will be insignificant.  If these sediments were not degraded anaerobically for the past 90 years, there is no reason to believe that they will do so after the reclamation.  The methane generation potential of the sediment to be left in-situ will therefore be estimated based on the top 2 m depth of sediment.

11.3.4      The capping of the reclamation would likely create underlying anaerobic conditions that favour degradation of organic matter by microbial activity in the contaminated sediment.  The end product of this degradation is biogas, which mainly consists of methane (CH4) and carbon dioxide (CO2).

11.3.5      The rate of biogas generation is dependent on the amount of organic matter, degradability of organic matter, extent of anaerobic conditions, temperature, and transport medium for bacteria (water).  Although the available information is limited, a theoretical calculation can be made for an estimate of biogas generation within the reclamation area.

11.3.6      From experience in several anaerobic degradation projects (with waste as well as sludge), it is known that the biogas formation can be described as a first order degradation process.  This process is characterised by high gas generation rates at the start, followed by an exponential decrease over the course of time.  Biogas generation can be calculated based on the available data on organic matter content or sediment oxygen demand (SOD).

11.3.7      Not all organic carbon present in the sediment would be biodegradable.  The SOD represents the biodegradable fraction of the organic carbon present in the sediment and, thus, is convertible to methane.  Under anaerobic conditions, all of the oxygen demand of degradable organic material is preserved in the methane formed.  The following equation shows that 4 g of oxygen demand would have a total yield of 1 g of methane (the molar mass of methane is half the molar mass of oxygen and two moles of oxygen are required to oxidise one mole of methane).

CH4     +          2O2      =    CO2  + 2H2O

No. of moles        1                      2

 

11.3.8      As an example, a sediment with a SOD of 200 mg m-3 will ultimately generate 50 mg of methane, equivalent to 0.07 litre of methane per m3 of sediment at standard temperature and pressure (STP).

11.3.9      It is assumed that 50% of the gas produced from anaerobic degradation of organic matter of the sediment is methane (the remainder being carbon dioxide).  This is true for substrates such as carbohydrates that are neither highly oxidised nor highly reduced:

2CH2O                                             CH4      +      CO2

11.3.10   On that basis, the mass of methane generated from unit mass of TOC is calculated as follows:

2C                                                   CH4      +     CO2

2 x 12 = 24                                       16

that is, methane potential = 16/24 = 0.67 times TOC

11.3.11   Assuming a SOD in the material to be contained in the future reclaimed land of 8,078 mg kg-1, the total methane potential would be 2,019 mg kg-1, or assuming a dry matter content of 53%, 3,803 mg kg-1.  However, SOD represents only a fraction of the organic carbon present in the sediment.  Based on a sediment TOC of 2.9% of dry matter and assuming that half is converted to methane (the remainder being carbon dioxide), methane potential would be about 19,625 mg kg-1 dry matter.  This implies that only 20% of TOC represents readily biodegradable organic matter.  Use of TOC to estimate methane potential therefore provides an over-estimate of that potential.  Furthermore, some organic substrates which are degradable aerobically (and which therefore contribute to SOD) are not degradable at all in anaerobic conditions.  Therefore, basing potential methane yield on SOD itself probably provides an over-estimate of methane potential. 

11.3.12   It is difficult to estimate the half-life of substrates in systems such as contaminated marine sediment.  However, at low substrate concentrations in engineered systems such as facultative ponds, half-lives of substrates in the anaerobic could be of the order of half a year.  In landfills, the average half-life of organic substrates could be 5 years.  Hence, for conservatism, the methane potential is calculated based on TOC rather than SOD because the former represents the extreme worst case, assuming all organic matter is biodegradable and convertible to methane.  In fact, as indicated above, probably only 20% of the organic carbon is readily degradable.  Thus, an analysis based on TOC alone will overestimate the impact by a factor of about five.

11.3.13   Based on the range of half-lives of 0.5 - 5 years, the peak annual methane potential would be between 13 and 75% of the total, that is, 2,551 – 14,719 mg kg-1.  The peak annual methane potential corresponding to a half-life of decay of 0.5 years, is actually not significant in terms of development because after two years over 90% will have degraded and the flux will have fallen proportionately to a rate less than that of the lower figure after the same time.  Therefore, the peak annual methane potential based on a half-life of 5 years is adopted for the calculations of potential methane gas emission for the comparison with the UK methane hazard assessment criteria.  A half-life of 2 years is also adopted for the calculation of potential methane gas emission to represent a worst-case scenario (as a half-life of 2 years will result in a higher flux rate at 2 years after reclamation than that resulting from a half-life of 5 years).  Table 11.3 shows calculations of the daily methane flux from the WDII reclamation.

11.3.14   The methane concentrations of the boundary layer at the surface of the WDII reclamation is also estimated as shown in Table 11.3 for the comparison with the guideline value (1% v/v) as stipulated in EPD’s Landfill Gas Hazard Guidance Note.  The boundary layer is assumed to be 1 m to represent the worst case scenario.


Table 11.3       Calculation of Methane Flux from the WDII Reclamation

 

Marine Sediment – Western Corner

Marine Sediment – Eastern Corner

Methane Hazard Assessment Criteria

Half-life cycle of 5years

Half-life cycle of 2years

Half-life cycle of 5years

Half-life cycle of 2years

Volume (m3)

42,422

42,422

6,732

6,732

-

Density (kg m-3)

1,370

1,370

1,370

1,370

-

Dry matter (% w/w)

53

53

58.6

58.6

-

Dry matter (kg m-3)

726.10

726.10

802.82

802.82

-

TOC (%)

2.93

2.93

1.72

1.72

-

TOC (kg m-3)

21.27

21.27

13.81

13.81

-

CH4 potential (kg m-3)

14.25

14.25

9.25

9.25

-

Peak annual CH4 potential (kg)

78,609

175,359

8,097

18,062

-

Total area (m2)

21,211

21,211

3,366

3,366

-

Total potential CH4 flux (kg m-2 per year)

3.71

8.27

2.41

5.37

-

Total potential CH4 flux (g m-2 per year)

3,706.06

8,267.36

2,405.44

5,365.98

-

Total potential CH4 flux (mol m-2 per year)

231.63

516.71

150.34

335.37

-

Total potential CH4 flux (L m-2 per year)

5,188.48

11,574.30

3,367.62

7,512.38

-

Total potential CH4 flux (L m-2 per day) (assuming 20% of TOC biodegradable)

2.84

6.34

1.85

4.12

18(a) – 432(b)

10(d)

Total potential CH4 flux (L m-2 per day) (assuming 100% of TOC biodegradable)

14.22

31.71

9.23

20.58

Potential CH4 concentration (% v/v) at the surface boundary layer (assuming 20% of TOC biodegradable)

0.28

0.63

0.19

0.41

1(c)

 

Potential CH4 concentration (% v/v) at the surface boundary layer (assuming 100% of TOC biodegradable)

1.42

3.17

0.92

2.06

Notes

(a)   UK Landfill Completion Criterion from Department of the Environment (1993), Landfill Completion.  Waste Management Paper No. 26A.  London: HMSO.

(b)   Carpenter’s guidance level from Carpenter, R. J. (1988), Building development on disused landfill sites - overcoming the landfill gas problem.  In: Proc. 5th International Solid Wastes Conference, Copenhagen, Denmark, Vol., 153-160. London: Academic Press.

(c)   Guideline value from Landfill Gas Hazard Guidance Note, EPD, HK.

(d)   Maximum “safe” rate of gas emission derived for WDII, as based on Department of the Environment (1993), Landfill Completion.  Waste Management Paper No. 26A.  London: HMSO.               

11.3.15   The above analysis is based on a number of broad assumptions that might affect the precision of the estimates.  Furthermore, it takes no account of biological methane oxidation that will probably occur in the upper layers of the sediment.  In the case of a uniform emission through a permeable, aerobic reclamation layer, methane (or part of it) can be oxidised microbiologically.  In the literature, oxidation efficiencies can be found of 2% up to 100%([8]).  For landfills, covered by a very permeable top layer, oxidation efficiencies were found in the range of 0 - 50%([9]).  High efficiencies will only occur when the fill material is well aerated (for example, by diffusion of air) and the gas is able to emit uniformly over the surface area.  Low efficiencies, however, will occur when the fill material is poorly permeable for gases and when the gas generation rate is rather high, so that concentrated emissions can take place via fissures, or other preferential pathways (for example, gravel layers).

11.4          Evaluation of Significance of Potential Gas Emissions

Significance of potential methane emissions with reference to the UK Guidance Values

11.4.1      As shown in Table 11.3, the predicted potential methane flux from the marine sediment left in-situ at the western corner of the WDII reclamation within the typhoon shelter is higher than that predicted from the eastern corner of the typhoon shelter reclamation.  The assessment of biogas risk associated with the WDII reclamation will therefore be based on the methane flux calculation for the western corner of the typhoon shelter to represent a worst-case scenario.

11.4.2      Taking the UK landfill completion criterion (that is, 18 L m-2 per day) as the standard, the predicted methane emission from the WDII reclamation based on a half-life of 5 years (2.84 L m-2 per day), assuming 20% of TOC biodegradable, is only 15.8% of this guide value.  This provides a safety factor of approximately 6.  Based on a half-life of 2 years, the predicted methane emission (6.34 L m-2 per day) is 35% of the UK landfill completion criterion, providing a safety factor of approximately 3.  The predicted methane emission based on the assumption of 100% TOC biodegradable, though which is highly unlikely, is also considered as a conservative estimate.  The methane emission (14.22 L m-2 per day) for a half-life of 5 years is found to be approximately 79% of the UK landfill completion criterion.  Under the worst case scenario of a half-life of 2 years, the predicted methane emission (31.71 L m-2 per day) is found to be approximately 1.8 times greater than the UK landfill completion criterion.

11.4.3      The calculations show that the predicted methane emission based on a half-life of 5 years, assuming 100% of TOC biodegradable, is about 3.3% of the Carpenter’s guidance level (that is, 432 L m-2 per day), providing a safety factor of approximately 30.  The predicted methane emission based on a half-life of 2 years, assuming 100% of TOC biodegradable, is about 7.3% of the Carpenter’s guidance level, providing a safety factor of approximately 14.  Under this worst case scenario, the predicted methane emission is well below the upper UK guide value, which is the level at which development would be restricted according to Carpenter’s guidelines.

11.4.4      Taking the “safe” rate of gas emissions derived for WDII from Waste Management Paper No. 26A on Landfill Completion as the standard (that is, 10 L m-2 per day), the predicted methane emission from the WDII reclamation, assuming 20% of TOC biodegradable, is about 3.5 times less than this guide value.  The predicted methane emission based on the worst case assumption of 100% TOC biodegradable is also considered as a conservative estimate.  The calculations show that the predicted methane emission (14.22 L m-2 per day), assuming 100% of TOC biodegradable, is approximately 1.4 times greater than the “safe” emission rate  (that is, 10 L m-2 per day).  Taking the worst case scenario of a half-life of 2 years, the calculations show that the predicted methane emissions are approximately 1.6 times less and 3.2 times greater than the “safe” emission rate, assuming 20% and 100% of TOC biodegradable, respectively.  

11.4.5      The derived maximum “safe” rate of gas emissions is based on a number of assumptions regarding the size and rate of ventilation of the ‘at risk’ room, and the permeability of the ground surface at the site.  It is therefore necessary to consider the most sensitive ‘at risk’ features of the proposed development at the WDII reclamation in order to determine the likelihood of methane emissions posing a significant risk and the need for mitigation measures.

11.4.6      The proposed land use at the western corner of the reclamation within the Causeway Bay Typhoon Shelter is either commercial use (office and retail) or a hotel development.  The estimated site area of the proposed development is 6,964 m2.  Any biogas emissions from the sediment beneath the reclamation will tend to pose limited risk to the above ground rooms in this proposed high rise development.  Rooms located at the ground level of the building, however, such as transformer and refuse collection rooms for example, may be susceptible to ingress of any biogas generated from the reclamation.  These rooms are usually provided with a relatively high rate of mechanical ventilation.  Other at risk voids may include utility (services) voids and lift pits.  The most sensitive ‘at risk’ room is considered to be the proposed underground car park which would be susceptible to ingress and accumulation of any biogas emissions from the reclamation.  It will therefore be necessary to ensure adequate ventilation of the underground car park to prevent the accumulation of any methane gas emissions to dangerous concentrations.  This precautionary measure and other recommended gas protection measures for both the ground level and underground rooms at the proposed development are discussed in Section 11.5.   An entertainment complex is under consideration for the eastern corner of the WDII reclamation within the typhoon shelter, with uses such as an indoor interactive theme park, game stalls, restaurants, shops and car parking.  The estimated site area of the proposed complex is 7,736 m2.  The most sensitive ‘at risk’ rooms are considered to be the proposed basement food court and underground car park which would be susceptible to ingress and accumulation of any biogas emissions from the reclamation.   From Table 11.3, it can be seen that the predicted methane emission based on the worst case assumption of 100% TOC biodegradable and a half-life of 2 years is approximately 2 times greater than the “safe” emission rate  (that is, 10 L m-2 per day).  It will therefore be necessary to ensure adequate ventilation of the basement floors to prevent the accumulation of any methane gas emissions to dangerous concentrations.  Precautionary measures are discussed in Section 11.5.

11.4.7      The development will include some cover in the form of non-permeable concrete or asphalt layers.  These layers decrease the possibilities for bacteriological oxidation of methane in the top layer.  This might result in more concentrated emissions or accumulation of methane in cavities.  Therefore, if the precautionary principle is to be applied, it is recommended to undertake methane gas monitoring in the immediate post-reclamation period to measure methane concentrations in the fill.

Significance of potential methane emissions with reference to EPD’s Landfill Gas Hazard Guidance Note

11.4.8      The predicted methane concentration at the surface boundary layer within the western corner of the WDII reclamation has been compared with the assessment criteria to represent a worst-case scenario. 

11.4.9      The methane concentration at the surface boundary layer from the WDII reclamation is estimated to be 0.28% (v/v) (assuming 20% of TOC biodegradable and a half-life of 5 years) which is 3.5 times less than the guide value of 1% (v/v), as stipulated in EPD’s Landfill Gas Hazard Guidance Note.  Based on the worst case scenario of a half-life of 2 years, the estimated methane concentration of 0.63% (v/v) is below the EPD’s guide value.

11.4.10   On considering the highly unlikely event of assuming 100% TOC biodegradable, the methane concentration at the surface boundary layer from the WDII reclamation is estimated to be 1.42% and 3.17% based on a half-life of 5 and 2 years, respectively, which is in exceedance of the EPD’s guide value.  It is therefore recommended that the above precautionary approach be adopted.  Mitigation requirements are discussed in Section 11.5 below.

11.5          Mitigation Measures and Further Work

11.5.1      The methane calculations provided above are based on numerous theoretical assumptions and there is virtually no precedent established on practical grounds against which they can be tested.  It is therefore recommended to establish gas monitoring boreholes immediately after reclamation and prior to development to determine actual rates of methane gas emissions generated from the marine sediment underlying the reclamation.  The predicted methane emissions based on the conservative assumption of 100% biodegradable TOC are well below the upper UK guidance value (which is the level at which development would be restricted according to Carpenter’s guidelines).  The recommended monitoring requirements are detailed below. 

11.5.2      The potential biogas risk has been assessed based on the predicted peak methane generation potential and total daily methane flux (based on the TOC results and assuming all organic matter is  biodegradable).  Based on this conservative approach, the predicted daily methane flux is higher than the UK “safe” rate of methane gas emission (as derived from Waste Management Paper No. 26A for methane ingress into an ‘at risk’ room within a building constructed on a restored landfill site).  As discussed in Section 11.2.8, the UK maximum “safe” rate of landfill gas emissions is based on a number of assumptions regarding the size and rate of ventilation of the ‘at risk’ room or void space.  This criterion was developed to determine when monitoring of landfill gas emissions at a restored landfill can be discontinued and when the site can be used for unrestricted development.

11.5.3      As sensitive ‘at risk’ rooms may be present at the proposed developments at the western and eastern corners of the typhoon shelter, both at ground level and below ground, it is recommended that a precautionary principle should be applied.  Given that mitigation measures to prevent the ingress and / or accumulation of any methane gas emissions generated from the reclamation may be very costly, it is recommended that monitoring of gas emission rates should be undertaken at the area of the proposed developments within the western and eastern corners at the WDII reclamation.  The results of the gas monitoring should be reviewed to determine the extent of mitigation measure requirements to be incorporated in the detailed design of the proposed development.

Gas Monitoring

11.5.4      Monitoring should be undertaken via purposely installed monitoring wells within boreholes drilled into the fill material.  The boreholes should be drilled down to the level of the groundwater (mean sea water level) and standard landfill gas-type monitoring wells installed.  During the drilling of boreholes, the safety and working procedures described in the EPD Landfill Gas Hazard Assessment Guidance Note (1997) should be followed.

11.5.5      Concentrations of methane gas should be measured using intrinsically safe, portable gas monitoring instruments.  Fluxes should also be measured if the emission velocities are not too low.  It is recommended that monitoring should be undertaken monthly for a period of at least one year prior to the commencement of construction works on the reclamation.  Details of the recommendations for methane gas monitoring are given in the EM&A Manual.

Precautionary Gas Protection Measures

General Guidelines

11.5.6      At this stage it is difficult to formulate specific guidelines on what measures would be required for the measured rates of gas emission as this would depend on the detailed design of the individual buildings to be constructed.  The following criteria may be used as general guidelines.  The maximum “safe” rate of methane gas emission of 10 L m-2 per day derived for WDII from the Waste Management Paper No. 26A on Landfill Completion is proposed to be adopted as the trigger value.

Scenario 1

11.5.7      If rates of methane emission are consistently much less than the trigger value (10 L m-2 per day), including monitoring occasions when atmospheric pressure is falling rapidly, then it is considered that the buildings will not require gas protection measures.

11.5.8      The trigger value is an area emission rate (that is, rate at which gas is emitted per unit area of the reclamation).  In order to convert this into an emission rate from a borehole, it is necessary to make an assumption about the "area of influence" of a freely venting borehole which depends on a number of factors.  A key factor is the ease by which gas can escape from the surface of the site.  For a site with cover in the form of low permeability paving or concrete, it would be expected that a borehole would have a much greater area of influence than if the site had soft landscaping.

11.5.9      To be conservative, it is proposed to adopt an area of influence of 20 m2 (radius of 2.5m)([10]), which would give:

·            Trigger value of 10 L m-2 per day x 20 m2  =  200 L per day emitted from the borehole

11.5.10   The criterion for “safe” flow rate from a free venting borehole becomes:

·            Flow rate of methane (in terms of litre per day) < 200 L per day  or

·            (Gas flow rate in terms of litre per day) x (concentration of methane in gas (in % gas)) < 200 L per day

Scenario 2

11.5.11   If the rate of methane emission frequently exceeds the trigger value or shows a rising trend such that future emission rates are likely to exceed the trigger value, then any buildings to be constructed on that part of the site will require some form of gas protection measures, that is,

·         (Gas flow rate in terms of litre per day) x (concentration of methane in gas (in % gas)) >  200 L per day.

11.5.12   The type of gas protection measures would be dependent on the design and use of the particular building.  A possible measure is the incorporation of a low gas permeability membrane in the floor slab of the building.  Further investigation may be required to determine the area of land which is affected by gas emissions.  The analysis and assessment of the results and design of any gas protection measures should be undertaken by suitably qualified and experienced professionals who are familiar with the properties of biogas and building protection design measures.

Scenario 3

11.5.13   If there are occasional exceedances of the trigger value for methane emission rate from a borehole or if there is a significant fluctuation of the monitoring results with some readings coming close to the trigger value, then any trends in the results will need to be assessed to determine their significance and the need for any building protection measures.  It may be necessary to undertake further monitoring by extending the monitoring period, for example, if a spuriously high reading is noted towards the end of the monitoring period or if it seems likely that future emission rates may exceed the trigger value.  The analysis and assessment of the monitoring results and design of any gas protection measures should be undertaken by suitably qualified and experienced professionals who are familiar with the properties of biogas and building protection design measures.

Scenario 4

11.5.14   If the rate of methane emission from any borehole frequently exceeds the upper UK guidance value of 432 L m-2 per day (that is, Carpenter’s guidance level at which it is recommended that development should not take place), or shows a rising trend such that future emission rates are likely to exceed this value, then no buildings should be constructed on that part of the site.  That is when:

·         Upper UK guidance value of 432 L m-2 per day x 20 m2  =  8,640 L per day  emitted from the borehole; or

·         (Gas flow rate in terms of litre per day) x (concentration of methane in gas (in % gas)) > 8,640 L per day.

11.5.15   Depending on the monitoring results, it may be necessary to incorporate a number of gas protection measures into the design of the proposed development.  Specific details cannot be provided until the results of the monitoring are available, and the proposed landuse and building design are known and confirmed.  A combination of different measures may be used for protecting both the ground level and underground structures at the development against possible risks due to biogas emissions.  Discussions would need to be held with the developer and architects to determine the protection measures which are the most appropriate and feasible.  Typical gas protection measures that may be adopted are described below.

Measures to Prevent Ingress of Gas into ‘At Risk’ Rooms

11.5.16   To prevent the ingress of methane gas into a building, a low gas permeability membrane may be incorporated in the design of the floor and any below ground walls of identified ‘at risk’ rooms (for examples, rooms housing electrical equipment, pumps or switchgear).  In addition, measures should be taken to avoid or seal any openings in the floor (for example, at services entry points).  Such techniques are commonly used where there is a risk of landfill gas entering a building and have been employed on a number of developments in Hong Kong.

11.5.17   There are various proprietary products available in the market and the specific details of their application will depend on the detailed design of the ‘at risk’ rooms.  Possible measures include gas-resistant polymeric membranes that can be incorporated into the floor or wall construction as a continuous sealed layer.  Membranes should be able to demonstrate low gas permeability and resistance to possible chemical attack.  Other building materials such as dense well-compacted concrete or steel shuttering also enhance resistance to gas permeation.  In all cases, extreme care is needed during the installation of the membrane and subsequent construction works to avoid damage to the membrane. 

Ventilation within ‘At Risk’ Rooms

11.5.18   As an additional measure for the protection of specific ‘at risk’ rooms, mechanical ventilation may be provided to ensure that if any gas enters the room it is dispersed and cannot accumulate to potentially dangerous concentrations.  For particularly sensitive rooms, such as below ground confined spaces which contain sources of ignition, forced ventilation may be used in addition to the use of a low gas permeability membrane. 

11.5.19   The basement car park proposed at the development would be susceptible to ingress and accumulation of any biogas emissions from the reclamation.  The basement car park ventilation system will be designed to ensure that the car park air quality guidelines given in ProPECC PN 2/96 Control of Air Pollution in Car Parks are achieved.  The minimum ventilation rate for a basement car park is 5 to 6 air changes per hour in order to comply with the EPD requirement on carbon monoxide concentrations within car parks.

11.5.20   It is recommended that several ventilation systems should be installed and evenly distributed within the basement car park.  Therefore, even during equipment failure, it is unlikely that the entire exhaust system would break down.  To cater for the situation of power failure, it is recommended that a back-up power supply shall be provided for the ventilation system so that certain designated exhaust systems would still operate.  Under normal conditions, the power failure should be rectified within several hours.

Protection of Utilities or Below Ground Services

11.5.21   Below ground ducts or trenches for the installation of utilities or services (for examples, telecommunications, gas, water, electricity supply or drainage connections) would be particularly prone to the ingress and accumulation of any biogas emissions.  It is therefore important to prevent such ducts and trenches acting as routes by which gas may enter buildings by avoiding, as far as possible, the penetration of floor slabs by such services.  In addition, any unavoidable penetrations should be carefully sealed using puddle flanges, low permeability sealant and / or membrane.

Precautions during Construction Works

11.5.22   Special care must be taken during the first two years of construction activities on the reclamation.  Sub-surface excavations into the mud layers might encounter gas occasionally, but not at levels likely to be dangerous provided that the gas vents freely to atmosphere.  Emission rates are unlikely to be sufficient to sustain a flame.  These gas bubbles will only occur for short periods, and therefore, as a precaution, smoking and naked flames in the vicinity of drilling activities and excavations of 1 m depth or more should be prohibited.

11.5.23   Precautions may be required to ensure that there is no risk due to the accumulation of gas within any temporary structures, such as site offices, during construction works on the reclamation area.  It may be necessary, for example, to raise such structures slightly off the ground so that any gas emitted from the ground beneath the structure may disperse to atmosphere rather than entering the structure.  A minimum clear separation distance of 500 mm, as measured from the highest point on the ground surface to the underside of the lowest floor joist, is recommended in the Landfill Gas Hazard Assessment Guidance Note, EPD (1997).

Precautions Prior to Entry of Below Ground Services

11.5.24   Following construction, accumulation of gas within any below ground services can pose a risk to the staff of the utility companies.  As a good working practice, prior to entry into any confined space within the reclamation site (such as manholes, underground culverts and utility casings), the gas atmosphere within the confined space should be monitored for oxygen, methane and carbon dioxide.  Personnel should be made aware of the potential dangers and advised to take appropriate precautions.

11.5.25   The working practices should follow the Landfill Gas Hazard Assessment Guidance Note, EPD (1997) guidelines as follows:

·         Any chamber, manhole or culvert that is large enough to permit access to personnel should be subject to entry safety procedures.  Such work in confined spaces is controlled by the Factories and Industrial Undertakings (Confined Spaces) Regulations of the Factories and Industrial Undertakings Ordinance.  Following the Safety Guide to Working in Confined Spaces ensures compliance with the above regulations.

·         The entry or access point should be clearly marked with a warning notice (in English and Chinese) which states that there is the possibility of flammable and asphyxiating gases accumulated within.

·         The warning notice should also give the telephone number of an appropriate competent person who can advise on the safety precautions to be followed before entry and during occupation of the manhole.

·         Personnel should be made aware of the dangers of entering confined spaces potentially containing hazardous gases and, where appropriate, should be trained in the use of gas detection equipment.

·         Prior to entry, the atmosphere within the chamber should be checked for oxygen, methane and carbon dioxide concentrations.  The chamber may then only be entered if oxygen is greater than 18% by volume, methane is less than 10% of the Lower Explosive Limit (LEL), which is equivalent to 0.5% by volume (approximately), and carbon dioxide is less than 0.5% by volume.

·         If either carbon dioxide or methane is higher, or oxygen lower than the values given above, then entry to the chamber should be prohibited and expert advice sought.

·         Even if conditions are safe for entry, no worker should be permitted to enter the chamber without having another worker present at the surface.  The worker who enters the chamber should wear an appropriate safety / recovery harness and, preferably, should carry a portable methane, carbon dioxide and oxygen meter.

11.5.26   In general, when work is being undertaken in confined spaces sufficient approved resuscitation equipment, breathing apparatus and safety torches should be available.  Persons involved in or supervising such work should be trained and practised in the use of such equipment.  A permit-to-work system for entry into confined spaces should be developed by an appropriately qualified person and consistently employed.

11.6          Conclusion

11.6.1      Organically enriched material is planned to be left in-situ at the WDII reclamation within the western and eastern corners of the Causeway Bay Typhoon Shelter.  As methane gas could be generated under anaerobic conditions, there is a potential for this gas to be released either during construction or after development of the reclaimed area.

11.6.2      The calculation of the total potential methane flux was overly conservative in nature in order to build-in a large margin of safety.  Conservative assumptions included the following:

·         All the TOC is readily biodegradable.

·         All the organic matter is degraded to methane and no re-oxidation in surface layers occurs.  (In fact, oxidation may occur in the upper layers of fill.  Methane passing up through such layers may be partially or even totally destroyed by oxidation).

·         Higher methane fluxes can be ignored as they are based on a half-life of only 0.5 year, which would result in 90% of the methane being lost to atmosphere prior to the proposed development on WDII reclamation.

·         A boundary layer of 1 m at the surface of the reclamation is assumed as a worst case scenario.

11.6.3      Assuming 100% of TOC is biodegradable, an extreme worst case scenario, the predicted methane emissions from the western and eastern corners of the WDII reclamation for a half-life of 5 years were found to be approximately 79% and 51%, respectively, of the UK landfill completion criterion.  Based on a half-life of 2 years, the predicted methane emission was found to be approximately 1.8 times greater than the UK landfill completion criterion for the western corner of the WDII reclamation, and approximately 1.1 times greater than the UK landfill completion criterion for the eastern corner of the WDII reclamation.  Under the worst case scenario of 100% biodegradable TOC, the predicted methane emissions based on half-lives of 5 and 2 years are well below the upper UK guidance value, which is the level at which development would be restricted according to Carpenter’s guidelines.  This suggests that the methane gas generation potential is not expected to pose a development constraint to the WDII reclamation.  These UK guidelines are considered to be consistent with current Hong Kong guidance. 

11.6.4      In view of the exceedance of the recommended maximum “safe” rate of methane emission (derived from Waste Management Paper No. 26A) under the worst case scenario of 100% biodegradable TOC and the identification of ‘at risk’ rooms at the proposed developments at the western and eastern corners of the typhoon shelter reclamation, it is recommended that monitoring of gas emission rates should be undertaken following the completion of the reclamation area at the proposed developments.  The review of the gas monitoring results would determine the need for gas protection measures to be incorporated in the building design to prevent the ingress and / or accumulation of any methane gas emissions to potentially dangerous concentrations.  Typical gas protection measures are described for both the ground level and below ground structures at the developments.

11.6.5      Precautionary measures to be taken prior to entry into any below ground services or confined space within the reclamation site are also recommended.  As a further precaution, naked flames should not be permitted during construction involving drilling or excavation. 

11.6.6      With the incorporation of the recommended gas protection measures in the design of the developments, if found to be necessary, together with the implementation of the other recommended precautionary measures, the risk to people and property due to biogas emissions from the WDII reclamation is considered to be low.  The proposed mitigation measures should be examined further at the detailed design stage with regard to the specific design details of individual buildings and the confirmed landuse.

 



([1])   Carpenter, R. J. (1988).  Building development on disused landfill sites - overcoming the landfill gas problem.  In: Proc. 5th International Solid Wastes Conference, Copenhagen, Denmark, Vol., pp 153-160. London: Academic Press.

([2])   Interdepartmental Committee on the Redevelopment of Contaminated Land (1990).  Notes on the Development and After-Use of Landfill Sites.  Guidance Note 17/78.  London: Department of the Environment.

([3])   Department of the Environment (1993) Landfill Completion.  Waste Management Paper No. 26A.  London: HMSO.

([4])   ERM- Hong Kong, Ltd. (March 2000).  Agreement No. CE 70/97, Green Island Development Engineering Investigation and Planning Review.  Environmental Impact Assessment Review - Biogas Assessment (Final).

([5])   Binnie Consultants Ltd. (1989).  Hydraulic and Water Quality Studies in Victoria Harbour, Mathematical Model Report, Part II – Calibration and Validation Report.  Volume 9.  The Sediment Transport Model.

([6])   Binnie Consultants Ltd. (1993).  Remote Survey of Soft Bottom Environments in Coastal Waters of Hong Kong (1993).

([7])   ERM-Hong Kong, Ltd. (1997).  Seabed Ecology Studies: Tathong Channel Final Report.

([8])   Hoeks, J. (1972).  Effect of leaking natural gas on soil and vegetation in urban areas, Wagenin­gen.

([9])   (i)    Orlich, J. (1990).  Methane emissions from landfill sites and water waste lagoons, Federal Environ­ment Agency, Berlin.

        (ii)   UK Department of the Environment (1993).  An assessment of methane emissions from UK landfills.

        (iii) US-EPA (1993).  Anthropogenic methane emissions in the United States: estima­tes for 1990.

([10]) ERM Hong Kong Ltd. (March 2000).  Agreement No. CE 70/97, Green Island Development Engineering Investigation and Planning Review.  Environmental Impact Assessment Review - Biogas Assessment (Final).