The
hazard identification process is a formal review to identify all hazards for
the LNG facility. The hazards identified with potential to cause loss of
containment can be broadly categorised as:
·
Internal and process related hazards;
·
Natural hazards;
·
External hazards; and
·
Intentional acts
Further
elaboration of the hazards under each category is included in the following
paragraphs.
For
all hazards assessed as having a frequency of less than 10-9 per
year, the frequency assessment will be documented but no quantification of
consequences will be performed.
All
scenarios with a frequency greater than 10-9 per year and potential
to cause fatalities have the consequences of the event quantified.
Hazard
scenarios are excluded from the consequence assessment if one of the following
conditions is satisfied:
·
The frequency is below 1 x 10-9
per year.
·
The frequency of a particular event is
significantly smaller than other causes of failure considered in the generic
frequency.
·
If the generic failure frequency is judged
to include events of such kind, then such events are not assessed separately.
·
If there are no consequences. If an
event can be shown not to cause a loss of containment then the event is not
considered further.
1.1
Internal and
process related hazards
1.1.1
Internal Hazards of LNG Storage Tanks
Overfilling
The
nominal capacity (i.e. usable capacity) of the tank is 180,000 m3.
The design unloading rate is 14,000 m3/hr and the unloading time is
about 18 hours.
Overfilling
of the inner tank may lead to overflow into the annular space between the inner
tank and the outer tank. The bottom of the annular space is provided with 9% Ni
steel up to 5m height. Furthermore leak detectors are provided to detect any
LNG leak in the annular space bottom. Therefore, any overfilling event, if it
ever occurs, can be detected and shutdown initiated. Also, the secondary
containment provided by the outer concrete wall lined with steel will be able
to contain this liquid.
There
are several layers of safeguards to prevent overfilling:
a)
The tank to which the cargo is to be
unloaded is identified before the arrival of the carrier, its level
measured and the volume of cargo to be unloaded is pre-determined and this
information is provided to the carrier. The total volume of cargo unloaded is
also continuously monitored during unloading (typically, the volume of
available space within the shore tanks is at least equal to the cargo volume to
be discharged from the carrier, i.e. ships would not normally be required to
unload cargo at multiple destinations);
b)
Continuous level measurement on tank
using four separate detection systems with at least two different types of
level measuring device; pre-alarm at normal maximum level in tank,
corresponding to the usable capacity;
c)
Level high alarm; this is set typically
with 3 to 5 minutes holding volume (between normal maximum level and high
level) at design unloading rate;
d)
High high level initiates trip of
shutdown valves in liquid inlet including transfer piping from jetty and
re-circulation lines (the trip is initiated by a 2 out of 3 voting of separate
level measuring devices of different type). This will stop further inflow of
liquid into the tank. High high level trip is typically set with about 3 to 5
minutes holding volume (between high level alarm and high high level trip). The
safety integrity level (SIL) of the high high level trip of liquid inlet will
be determined during detailed design, however, SIL 2 classification is typical
for this instrumented protective system which means that the probability of
failure on demand will be less than less than 0.01;
e)
There is further holding volume of
about 10 to 15 minutes at design unloading rate between the high high trip
level and the inner suspended deck level before liquid can overflow through the
suspended deck to the annular space (it may be noted that the actual
height/volume between normal maximum level and the overflow level is determined
based on sloshing height for the safe shutdown earthquake event; typical values
are indicated above).
Based
on the above, it can be seen that there is sufficient time (more than 10
minutes) for operator intervention in addition to the provision of high
integrity instrumented protective system (i.e. high high level trip).
Rollover
Stratification,
i.e. formation of two distinct layers of different density may occur in an LNG
tank due to filling of cargo of different density than the liquid already in
the tank or due to preferential boil-off in the tank resulting in a layer of
more dense liquid at the top (due to evaporation of lighter components) as
compared to the lower layers (where the boil-off is suppressed by the
hydrostatic head but the liquid superheats due to heat ingress and becomes
warmer and less dense) [1]. Stratification may also occur due to presence of sufficient
nitrogen in LNG, typically more than 1%. Preferential boil-off of N2 results in a
layer of less dense liquid at the surface.
The
phenomenon of rollover occurs when the interface between the layers becomes
unstable, leading to rapid mixing of contents of the two layers. As the
superheated liquid from the lower layer rises to the surface, it gives off
large amounts of vapour leading to potential overpressure of the tank.
There
are a number of safeguards to detect and prevent stratification. These include:
a)
Temperature and density gradient
measurement along the tank liquid column;
b)
Provision for circulation of tank
contents through the operation of in-tank pump. Content from tank bottom is
recirculated to the top, thus releasing any superheat and promote mixing;
c)
Provision for filling of tank from the
top or from the bottom depending on the relative density of cargo and the tank
contents;
d)
Regular sampling and analysis of
boil-off gas including monitoring of boil-off gas quantity.
The
tank is also protected by relief valves in the event of de-stratification
leading to vapour generation. Relief valves are sized for rollover case as per
EN 1473 requirements.
Inner Tank
Leak
A
sketch of a typical full containment tank is shown in Figure 1.1.
The
main features of a full containment tank are that the liquid LNG is fully
contained within a self-supporting inner 9% Nickel steel, surrounded by loose
perlite insulation while the vapour is contained within a surrounding concrete
outer tank (which includes the slab, the wall and the dome, all constructed of
pre-stressed concrete). The concrete outer tank serves as secondary containment
and is also capable of containing the liquid and of controlled venting of the
vapour resulting from leakage of the inner tank, should one occur.
A
9% Ni steel plate is provided as liner along the inner surface of the outer
shell at the bottom up to a height of typically 5m from the base. This protects
the lower wall section of the outer tank, mainly the wall to base slab
connection in the event of leakage.
A
carbon steel plate lining is provided along the inner surface of the outer
shell and roof (above the bottom Ni plate liner) to act as vapour barrier (i.e.
to prevent vapour leakage through the concrete as well as to prevent moisture
ingress from the outside).
Figure 1.1 Typical
Structure of an LNG Storage Tank
The
suspended deck is constructed of aluminium plates and is supported by
suspension rods of stainless steel from the outer tank. Openings are provided
on the suspended deck for vapour communication between the inner tank and the
outer tank so as to ensure equilibrium of gas pressure on both sides.
Insulation is provided over the deck to minimise heat leak from the outer shell
to the liquid surface.
There
are no penetrations through the outer wall or the inner tank shell. All piping
to the inner tank is routed through the tank roof.
The
tank will be constructed in accordance with BS 7777 [2].
For
the capacity of tanks considered for this project, the concrete outer shell is
typically about 0.8m thick and can withstand impact loading from projectiles.
In
the case of a slab on the ground, installing an electrical heating system in
the concrete base slab prevents the freezing of the base slab and the frost
heave propagation in the ground beneath the foundation. Heating system control
and monitoring is provided.
There
are a number of design features to virtually eliminate any leakage from the
full containment tank to the atmosphere:
a)
Because all piping is routed through
the tank roof, there are no through penetrations in the outer shell or the
inner tank. Therefore the potential for any connection failure leading to
complete loss of tank inventory is eliminated;
b)
Outer tank (of pre-stressed concrete)
is designed to hold the cold LNG liquid;
c)
Inner tank is constructed of low carbon
9% Nickel alloy steel which is heat treated. The plate thickness varies from
about 10mm at the top to about 30mm to 40mm thick at the bottom. The material
remains ductile and crack resistant at cryogenic temperatures and is also of
high strength and toughness. This material is not subject to brittle failure
when exposed to cold temperature.
d)
Tests performed on 9% Ni steel plates
and welded assemblies show good performance against fatigue [3];
e)
In the event of any leakage from the
inner tank due to crack in the weld or other defect, the leakage rate will
remain small. The liquid will be contained in the annular space. Leak detectors
in the form of thermocouples are provided along the annular space to detect
leakage. Operator intervention is possible to empty the tank contents and
isolate the tank for inspection and repair. Liquid leakage into the annular
space is likely to result in additional vapour generation due to contact with
warmer surfaces including the perlite insulation. The relief valves sized for
the rollover case will be able to handle vapours resulting from liquid leakage
into the annular space in the event of a crack on the inner tank;
f)
A 5m high 9% Ni plate at the lower wall
section of the outer tank prevents any damage to the base slab to wall
connection due to liquid leakage.
The
engineering, construction, commissioning, and operation procedures for the
inner tank have been developed to ensure the highest level of safety and
reliability of the tank systems. For example, there are stringent QA/QC
procedures specified for material qualification and welding qualification,
material tracing and stamping, staggered vertical welds in construction,
commissioning check, etc. Such measures and procedures when executed by highly
experienced and competent contractors would virtually eliminate the occurrence
of gross human errors in material specification and qualifications.
The
long term LNG operation experience has demonstrated that there has been no
reported loss of containment incidents involving full containment tanks.
It
is also noted here that the full containment tank design offers significant
improvements over single containment and double containment tank designs which
have been prevalent earlier. More than 70 to 80% of the aboveground tanks
currently in service are either single containment or double containment tanks.
Overpressure
The
LNG tank is normally operated between 50 to 250mbarg. The tank is designed for
a maximum pressure of 290mbarg.
Overpressure
in tank may be caused by several factors:
a)
Normal boil-off due to heat leak from
ambient;
b)
Vapour displacement during filling
operation;
c)
Variation in atmospheric pressure (i.e.
drop in atmospheric pressure);
d)
Flashing of incoming liquid if it is at
a higher temperature than the bubble point of liquid at tank pressure.
Overpressure
can result in failure of the tank secondary containment. However, there are a
number of safeguards provided against overpressure:
a)
Normal boil-off vapours from the tank
is routed to a boil-off compressor where the vapour is compressed and sent for
re-liquefaction in the recondenser using the cold liquid pump-out from the
tank;
b)
Vapour generated due to displacement
during tank filling is returned to the ship through a blower (to provide the
required head for transfer) or compressed by a separate high pressure
compressor and routed to the sendout gas header;
c)
The tank pressure is continuously
monitored by two sets of pressure measurements;
d)
A pressure control valve is provided on
the tank to route all the excess tank vapours to a vent stack. The vent stack
height and tip will be determined such that vapours discharged will disperse
safely or if ignited, the radiation on the equipment and buildings adjoining
the stack are within permissible limits as per EN 1473. The pressure control
valve relieving to stack is typically designed for all overpressure cases under
normal operations (the maximum case is typically the ship unloading case);
e)
An independent high high pressure trip
is provided which will initiate shutdown of unloading operations (to stop
liquid inflow);
f)
Relief valves are provided on the tanks
which are sized for all the cases of overpressure. The maximum case is
typically the ship unloading case for normal operations. The governing case for
relief valve is however, the rollover case, which is an emergency case. The
relief valve discharge is routed to the stack.
Underpressure
The
LNG tank is normally operated between 50 to 250mbarg. The tank is designed for
a minimum pressure of typically -5mbarg.
Underpressure
may be caused by several factors:
a)
Pump-out of liquid;
b)
Increased compressor suction due to
control malfunction;
c)
Variation in atmospheric pressure (i.e.
rise in atmospheric pressure).
Under
normal operating conditions, the boil-off generated due to heat leak is
sufficient to prevent under pressure condition. Underpressure or vacuum
conditions below –5mbarg due to control malfunction can cause failure of the
tank containment. The tank bottom may be sensitive to vacuum and could get
lifted upwards.
There
are a number of safeguards in place:
a)
Continuous monitoring of tank pressure
by two sets of pressure measurement;
b)
Low pressure alarm;
c)
Low-low pressure will trip the boil-off
gas compressors and in-tank pumps and thus prevent further fall in tank
pressure;
d)
Pressure control valve provided to
inject external gas from the sendout gas header into the tank;
e)
Vacuum relief valves are provided which
are typically sized for maximum vapour flow arising from compressors and pumps
in operation. The operation of vacuum relief will lead to air-ingress into the
tank and thereby avoid collapse of the tank. The operation of vacuum relief is
envisaged as a measure of last resort.
1.1.2
Other Tank Related Hazards
Failure
of Foundation/Ice Heave
Ice
heave could occur in the event of a failure of the base slab heating system
over a long period. This may lead to a crack in the base slab leading to
failure of the tank base.
The
base slab heating is controlled by temperature sensors. Furthermore redundant
heaters with automatic switchover and redundant power supply source are
provided. Provision is also made to replace the heaters if required while the
tank is in service. Even if the heaters were to fail, it will be long time
before the ground would freeze leading to potential failure due to ice heave.
Operator intervention is possible.
Material
Defect/Structural Defect/Construction Defect
Material
defect may occur due to wrong materials being used in tank construction.
Construction defect may result in poor welding. Structural failure of the
concrete outer tank may occur, again due to poor construction or design.
In
all of the above cases, quality control procedures including testing
requirements during the design and construction and monitoring during operation
are the main means to mitigate the hazard.
The
design code EN 1473 [4] outlines a number of procedures including the
following:
a)
Monitoring of concrete, every quarter
of the concrete wall or every 5,000m3 of concrete;
b)
Testing of concrete outer wall by air
pressure up to 125% of design;
c)
Hydrostatic test of the inner tank.
Additional
precautions against failure at low temperature include gradual cooling of the
tank at a rate of 50°C/hr and gradual introduction of liquid with sufficient
waiting period at different levels to monitor any leakage.
Maintenance
of In-Tank Pump/Dropped Object
In-tank
pumps are provided to pump-out liquid from the tank. This eliminates the need
for nozzle penetrations through the tank shell. Maintenance of the in-tank pump
will require the lifting of the pump from the tank bottom through the pump well
to the tank roof. It is then carried from the tank roof to the ground level for
transport to the maintenance workshop. The removal of the pump is undertaken
while the tank is in service. The liquid in the pump well is displaced by
nitrogen and the pump is then lifted from its position at which point the foot
valve (at the bottom of the well, which normally remains in open position due
to the weight of the pump) gets closed. This prevents liquid entry into the
pump well during the lifting operation.
The
main hazard during this operation arises from accidental drop of the pump
(which weights about 2 tonnes) due to failure of the sling. This may cause
damage to the inner tank base plate leading to potential leakage from the inner
tank. It is unlikely to cause damage to the concrete base. This hazard can be
mitigated by appropriate lifting procedures, including the use of dual hoist.
Any leakage from the inner tank will be contained by the outer tank.
1.1.3
Tank Failure Frequency
The
usual approach to estimating failure frequencies is to use historical databases
of failures of similar facilities. However, there have been no failures of full
containment LNG storage tanks to date. Also, the experience is limited to about
5000 tank-years. The available data are therefore insufficient to make
statistical estimates of the failure frequencies. The approach in the
literature has been to base an assessment on more generic data such as that
from single containment tanks and then apply reduction factors and expert
judgement to take credit for the additional protection offered by a full
containment tank. The Purple Book [5] takes such an approach to derive a
frequency for catastrophic release from a full containment tank as 1 x 10-8
per tank-year.
Other
studies [6-12] into the failure frequency of single and double containment
tanks provide numbers similar to the Purple Book. From these studies it becomes
clear that the generic frequency data for ‘catastrophic’ failures, on which the
Purple Book analysis is based, includes any failure exceeding the ‘large leak’
definition, which is about a 50mm hole. The catastrophic failure frequency of
10-8 per tank-year for full containment tanks should therefore be
interpreted as inclusive of not only complete instantaneous tank failures but
also large leaks.
This
is consistent with comments in the Purple Book to the effect that all
catastrophic ruptures leading to a release to the atmosphere are partly (50%)
modelled as instantaneous release and partly (50%) as a continuous release
within 10 minutes.
Based
on this, a failure frequency of 1x10-8 per tank-year was adopted in
the current study. The terminal may eventually have 3 LNG storage tanks and so
the failure frequency was taken to be 3 x 10-8 per year.
This
failure frequency includes all the causes discussed above, namely
embrittlement, overfilling, rollover, overpressure, underpressure, ice heave,
material/construction defects and maintenance hazards. It is also common practice
[13] to take this frequency as inclusive of natural hazards since the generic
failure frequencies calculated in the literature include failures caused by
natural events such as earthquakes etc.
1.1.4
Internal and Process Hazards for Piping
and Equipment
The
failure rate of the process areas and piping are well documented and the values
used are given in Annex 13A6.
1.2.1
Seismic Hazard
GEO
studies conducted in the last decades indicate that Hong Kong SAR is a region of
low seismicity (e.g., GCO, 1991 [14]; GEO, 2002-2004 [15]). The seismicity in
the vicinity of Hong Kong is considered similar to that of areas of Central
Europe and the Eastern areas of the
For
this project, the full containment LNG tanks will be designed per the European
Standard EN 1473 (1997) [4] and British Standard BS 7777(1993) [2]. These
documents specifically exclude catastrophic failure of full containment tanks
designed, fabricated, erected, inspected, and tested in accordance with the
requirements contained in the codes. EN 1473 lists scenarios to be considered
in the required QRA and states that “no collapse is considered for these tank
types”.
In
terms of seismic risk category, LNG facilities are “essential/hazardous
facilities”, rather than “safety critical facilities” such as nuclear related
structures. Hazardous facilities are those that contain large quantities of
hazardous materials, but the release of those materials would be contained
within the boundaries of the facilities and the impact to the public would be
minimal.
For
seismic design in the LNG industry, a two-tier design approach is stipulated,
within the same framework of the risk category seismic design philosophy used
for nuclear facilities [17]. The Operating Basis Earthquake (OBE) is the
maximum earthquake for which the structure sustains no permanent damage and
restart and safe operation can resume after the earthquake. The OBE event has a
return period of 475 years. The Safe Shutdown Earthquake (SSE) is the maximum
earthquake for which the structures may sustain some permanent damage, but
there is no loss of overall structural integrity and containment of contents.
The SSE event has a return period of 10,000 years, which is the same as that
stipulated for the highest class nuclear facilities (Class 5). In addition, the
prescribed seismic design criteria for LNG tanks includes a load case for an
event less frequent than the SSE basis failing the inner tank followed by an
operating basis earthquake (OBE) aftershock acting on the outer tank. The
potential failure of the tank due to this event is not expected to occur in
The
full containment LNG tanks for this project will be founded on competent rock
or densely piled foundation. Studies conducted by LNG tank manufacturers and
constructors (e.g., Technigaz, 2003 [18]) have demonstrated that the full
containment tank of similar capacity to that proposed for this project and
designed by following EN 1473 and BS 7777 standards has the capacity to
maintain its structural and containment integrity for seismic design motions as
stipulated in Eurocode 8 [19] having up to 2.6g of peak ground acceleration
(PGA) for a rock site. This level of design earthquake motions on the bed rock
far exceeds the worst earthquake event ever recorded on a rock outcrop site
anywhere in the world. The SSE having a return period of 10,000 years
corresponds to PGA of about 0.5g based on latest seismic hazard studies
conducted for
It
is noted that a review of the earthquake resistance of LNG tanks to seismic
demand was carried out in Japan by a national examination committee following a
powerful earthquake with a PGA of 0.8g in southern Hyogo prefecture in 1995
[20]. The review concluded that the currently implemented standards are
sufficient to maintain structural integrity of LNG tanks and prevent gas leaks
even in an extremely rare and powerful earthquake. Note that an earthquake with
a PGA of 0.8g is well within the seismic design capacity for the LNG tanks in
this project which will be built to EN 1473 and BS 7777.
In
consideration of the seismic design requirements and the capacity and
reliability of LNG tanks to resist seismic demand, it is concluded that the
proposed full-containment LNG tanks will maintain structural integrity in the
1.2.2
Subsidence
Excessive
subsidence or differential settlement of ground may lead to failure of the
structures and ultimately potential loss of containment. This hazard is
relevant to facilities built on reclamation land or poor ground without proper
treatment or proper foundation design. For the Black Point terminal, the
original two tanks will be founded on competent rock and hence excessive site
subsidence or differential settlement is not expected. The future phase third
tank will be built on densely piled foundation founded on the bed rock in the
reclaimed area. Such foundation design prevents the occurrence of excessive
site subsidence or differential settlement.
For
the processing facilities at Black Point, a pile foundation design will also be
adopted to prevent any impact of subsidence or settlement on the equipment and
piping.
Based
on the above, the foundation design and piping system design address the
potential hazard of excessive subsidence and differential settlement of
foundation. There is therefore no basis to presume that the facility will be
more prone to subsidence than other facilities in the world and hence the
generic failure frequencies will cover scenarios involving subsidence.
1.2.3
Lightning
Lightning
strike can ignite flammable vapour discharges from vents and stacks. Lightning
strike has been the one of the causes of petroleum tank fires. However, this is
applicable to cone roof tanks and floating roof tanks. In the case of cone roof
tanks, the tank vent is in direct communication with the atmosphere. Breath-in
and breath-out occurs during withdrawal of liquid from tank and during filling
respectively. Vapours in flammable concentration may be generated which upon
ignition at the vent tip due to lightning strike can flashback to the liquid
inside (flame arrestor provided at the vent prevents such flame flashback). In
the case of floating roof tanks, vapours generated due to seal leaks may get
ignited.
The
above scenarios are not applicable to an LNG tank, which is a dome roof tank
and is maintained under pressure of about 50 to 250mbarg. A lightning strike
would have no impact on an LNG tank.
1.2.4
Landslides
At the site there is up to 10m of colluvium and weathered
rock material over competent rock. The colluvium is up to 2m thick and there
are also occasional large boulders.
The excavations made to create the tank platforms will give
rise to soil slopes at the upper part with a steeper rock slope below. Any
boulders above these slopes will either be removed or secured to the slopes.
The soil slopes created by the excavation will be secured by way of soil nails
in accordance with
Failure of the soil slopes will have no impact on the LNG
storage tanks. The external concrete tank construction can readily withstand
the impact of soil flow material without any compromise to the containment
function of the tank.
The risk of failure of the underlying rock slopes is
negligible. Rock slopes are at their most dangerous during construction. This
is because the exact nature of the state of the rock strength and fissure
patterns cannot be discerned with confidence until after the excavation is
completed. During the excavation however the rock can be logged and fracture
planes readily identified and any possible failure mode treated by mechanical
support. The possibility of future adverse water conditions within the rock
will also be controlled by drainage measures installed during excavation. The
degradation of the rock surface with time is extremely slow and therefore this
method of construction effectively guarantees that the rock slope will be
permanently stable.
1.2.5
Hill Fires
Hill
fires are a fairly common phenomenon in
The
terminal will have onsite landscape management to avoid the presence of
combustible vegetation near the LNG storage tanks and process areas. This will
prevent offsite hill fires from spreading to onsite areas. A study by Giribone
[3] shows that the stability of the concrete storage tanks is not jeopardised
by a fire scenario with an incident heat flux of 50kW/m2 (which is
higher than the maximum allowable flux of 32 kW/m2 as per the design code EN 1473) over a
period of 8 hours. There is no conceivable mechanism for a hill fire to produce
such radiation fluxes given the lack of vegetation near the tanks and process
areas.
1.2.6
Storm Surges and Flooding
If
the LNG storage tanks or piping become submerged under water, it is possible
for buoyancy forces to lift the pipes/tanks, causing damage and possible loss
of containment.
Flooding
from heavy rainfall is not possible due to the coastal location of the site.
The slopes of the natural terrain will drain water to the sea. The primary
hazard from typhoons is the storm surge. Winds, and to a lesser extent
pressure, cause a rise in sea level in coastal areas. In general, storm surges
are limited to several metres unless channelling effects from the coastline
exasperate the surge. Black Point’s location on the western tip of the
The
terminal facilities, located 6m above sea level are therefore protected against
any risk from storm surges, waves and other causes of flooding.
1.2.7
Tsunami
Similar
to storm surges, the main hazard from tsunamis is the rise in sea level and
possible floatation of piping and tanks. The highest rise in sea level ever
recorded in Hong Kong due to a tsunami was 0.3m high [21], and occurred as a
result of the 1960 earthquake in Chile, the largest earthquake ever recorded in
history at magnitude 9.5 on the Richter scale. With tanks and equipment
positioned 6m above sea level, the effect of a tsunami on the terminal is
considered negligible.
The
reason for the low impact of tsunamis on Hong Kong may be explained by the
extended continental shelf in the South China Sea which effectively dissipates
the energy of a tsunami, and also the presence of the Philippine Islands and
Seismic
activity within the
The
terminal has been designed with due consideration of sea levels, tsunamis,
waves and even rising sea levels from global warming. Being located 6 mPD, the
terminal is protected against all causes of flooding.
1.2.8
Summary of Natural Hazards
The
terminal site and design of the facility are such that there will be no special
risks from natural hazards. Natural hazards are therefore not treated
separately in the analysis but are included in the generic failure frequencies
(Annex 13A6).
1.3.1
Aircraft Crash
The
Black Point site does not lie within the flight path of Chek Lap Kok (Figure 1.2). Based on these figures, it is
seen that the Black Point site is about 10km from the runways and hence 10km
from the arrival and departure flight paths.
Figure
1.2 Flight
Paths at
The
frequency of aircraft crash was estimated using the methodology of the HSE
[24]. The model takes into account specific factors such as the target area of
the proposed hazard site and its longitudinal (x) and perpendicular (y)
distances from the runway threshold (Figure
1.3). The crash frequency per unit ground area (per km2) is
calculated as:
(1)
Where
N is the number of runway movements
per year and R is the probability of
an accident per movement (landing or take-off). F(x,y) gives the spatial distribution of crashes and is given by:
Landings
(2)
for km
Take-off
(3)
for km
Equations 2 and 3 are valid only for the specified range
of x values. If x lies outside this range, the impact probability is zero.
Figure 1.3 Aircraft
Crash Coordinate System
NTSB
data [25] for fatal accidents in the U.S. involving scheduled airline flights
during the period 1986-2005 are given in Table
1.1. The 10-year moving average suggests a downward trend with recent years
showing a rate of about 2 x 10-7 per flight. However, only 13.5% of
accidents are associated with the approach to landing, 15.8% are associated
with take-off and 4.2% are related to the climb phase of the flight [26]. The accident
frequency for the approach to landings hence becomes 2.7 x 10-8 per
flight and for take-off/climb 4.0x10-8 per flight. The number of
flights at Chep Lap Kok for year 2011 is conservatively estimated at 394,000 (a
50% increase over 2005).
Table 1.1 U.S
Scheduled Airline Accident Rate [25]
Year |
Accident
rate per 1,000,000 flights for accidents involving fatalities |
10-year
moving average accident rate per 1,000,000 flights |
|||||||||||
1986 1987 1988 1989 1990 1991 1992 1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 |
0.14 0.41 0.27 1.10 0.77 0.53 0.53 0.13 0.51 0.12 0.38 0.30 0.09 0.18 0.18 0.19 0.00 0.2 0.09 0.27 |
- - - - - - - -
|
Considering
landings on runway 25R for example, the values for x and y according to Figure 1.3 are 0.4 and 10.0km
respectively. Applying Equation 2
gives km-2. Substituting this into Equation 1 gives:
/year/km2
The
number of plane movements has been divided by 8 to take into account that half
of movements are take-offs and only a quarter of landings use runway 25R. This
effectively assumes that each runway is used equally and the wind blows in each
direction with equal probability.
The
target area is estimated at 15,000m2 or 0.015km2 (3 tanks
of 80m diameter). This gives a frequency for crashes into the tanks associated
with landings on runway 25R as 2.0 x 10-9 per year. Repeating the
calculation for landings and take-offs from all runways gives the results shown
in Table 1.2.
Table 1.2 Aircraft
Crash Frequency onto
Runway |
Landing
(per year) |
Take-off
(per year) |
07R 07L 25L 25R |
0 0 1.5 x 10-9 2.0 x 10-9 |
6.9 x 10-12 3.1 x 10-11 0 0 |
Total |
4.5 x 10-9 |
3.8 x 10-11 |
The
crash frequencies for take-offs are well below 10-9 per year. Impacts
from aircraft landing accidents have a frequency close to the 10-9
per year threshold. However, the storage tanks will be cut into the hillside at
the Black Point site. There will be no line of sight from the thresholds of
runways 25L and 25R to the LNG storage tanks; and with the tanks tucked in
closely behind the hillside, impact from an aircraft will be much less likely
than indicated by Table 1.2. Assuming
a shielding factor of 0.1 gives a total impact frequency of 4.5 x 10-10.
The combined frequency of all take-off and landing crashes onto the LNG tanks
from activities on all runways is less than 1 x 10-9 per year.
Aircraft crash is therefore neglected from the analysis.
The
process units have a smaller area than the tanks and will also be shielded by
the hill. Crashes into process areas are hence neglected from the analysis.
1.3.2
Helicopter Crash
Helipad
Activity
The
Black Point Power Station has a helicopter landing pad although the frequency
of use is low with perhaps one landing/take-off per week. The approach, landing
and take-off stages of an aircraft flight are associated with the highest risk
and therefore the possible impact of helicopter crashes on the LNG terminal
facilities were assessed.
Historical
data show that helicopter accidents during take-off and landing are confined to
a small area around the helipad [24]. 93% of accidents occur within 100m of the
helipad. The remaining 7% occur between 100 and 200m of the helipad. There have
been no serious helipad related incidents resulting in a crash beyond 200m of
the helipad.
The
distance of the existing helipad from the proposed LNG terminal is
approximately 900m. This is well beyond the range of accidents associated with
helipad activity. It is therefore concluded that the terminal will not be
exposed to any impact risks from helicopters using the helipad.
Passing Helicopters
Although
take-off and landings present the greatest portion of risk from a flight,
crashes during the in-flight stage of a journey may also occur. Black Point,
however, does not lie near any helicopter flight paths. There are Government
Flying Service helicopters in use in
The
CMPT Reports [27] gives a frequency of in-flight accidents of 1.2 x 10-5
per flying hour. However, only 17% of these are severe enough to cause a
fatality. Assuming that incidents involving fatalities are a reasonable measure
of uncontrolled crashes that may impact a facility, then the frequency becomes
2.0 x 10-6 per flying hour. The Government Flying Service conducted
4529 hours of operation in 2005 [28]. Assuming that a crash can occur anywhere
within the 2922 km2 of
The
frequency of helicopter crashes into the process area is small compared to the
frequency of internal and process related failures. As an example, the
vaporisers occupy an area of approximately 6000m2. A crash into the
vaporiser area would have a frequency of 1.8 x 10-8 per year based
on the above calculations. This would undoubtedly cause damage; however, the
generic failure frequency of all vaporisers combined is 8.5 x 10-5
per year. The additional hazard from helicopter activities is 3 orders of
magnitude smaller and may be neglected with negligible change in the risk
calculations. Hazards from helicopters are therefore not treated separately but
are covered by the generic failure frequency.
Consequence of Helicopter Impact
There
have been several studies related to the possible impacts of aircraft
collisions with hazardous facilities such as nuclear power stations. A study by
the Nuclear Energy Institute [29] investigated the damage that could be caused
by a fully loaded wide-bodied Boeing 767 crashing at 350 mph (560 km/h) into a
nuclear reactor containment structure. These containment buildings are
cylindrical shaped buildings with a dome roof, typically 140 feet high and 140
feet diameter. They are made of pre-stressed concrete with wall thicknesses
from 3.5 to 4.5 feet. This is very similar to the construction of LNG storage
tanks, which have a concrete wall of about 0.8m thickness. The conclusions of
the report were that the concrete containment would not fail from such an
impact.
In
another study [13], the consequence of a Boeing 767 commercial aircraft
crashing into an LNG storage tank was specifically assessed. It was concluded
that aircraft are constructed from mostly soft materials and only the core of
the engines is capable of penetrating an LNG full containment tank. Further,
the engine would need to impact at near perpendicular incidence otherwise the
engine will simply deflect off the tank.
These
studies demonstrate the structural strength of the LNG storage tanks. They are
designed to withstand major impacts. Naturally, a helicopter crash is very
different from a 200 tonne airliner travelling at 560 km/h. Most helicopter
crashes have an impact velocity below 50 m/s [24]. A fully loaded 5-tonne
Sikorsky S76C with an impact velocity of 50 m/s would have a kinetic energy 390
times less than the Boeing 767 analysed by the Nuclear Energy Institute. It is
concluded that a helicopter crash will not cause a failure of the LNG storage
tanks.
Summary
Activities
at the helipad will not impose any risks on the terminal. The frequency of
passing helicopters crashing into the storage tanks was estimated at 1.2 x 10-7
per year, however, a helicopter impact would not cause a failure of a tank.
An
impact into process areas or piping (including the piping on the LNG tanks)
could cause damage but the frequency of such events is much lower than generic
failure frequencies. The additional risk from helicopter activity is
negligible. Scenarios involving helicopter activities were therefore not
treated separately but are covered by the generic failure frequency.
1.3.3
External Fire and Explosion Hazards
The
LNG tank may be exposed to radiation and fire effects as well as explosion overpressure effects including
flying debris arising from ignition of flammable gas leak in process units
located adjoining an LNG tank or neighbouring facilities. A study by Giribone
et al [3] shows that a full containment tank with outer concrete shell (of
about 0.8m thick wall and 0.5m thick roof) can withstand fire and flying debris
impacts without any damage to the tank containment.
The
study by Giribone shows that the stability of the concrete structure is not
jeopardised by a fire scenario with an incident heat flux of 50kW/m2 (which is
higher than the maximum allowable flux of 32 kW/m2 as per the design code EN 1473) over a
period of 8 hours. Although through cracks in the concrete structure may occur,
the structural integrity of the tank is not compromised.
The
study by Giribone also shows that a flying debris of 2000kg in mass (a typical
4” valve weighs no more than 125kg) travelling at 50m/s causes no significant
impact on the concrete structure, though cracks may be created by such an
impact. The abovementioned studies [13, 29] suggest that the tanks can
withstand considerable greater impact.
Based
on the above it can be concluded that the outer concrete structure of a full
containment tank provides significant resistance against external fire and
explosion hazards. Failure of the tank due to such events will not occur. It
may be also be noted here that the extent of process equipment and piping is
very limited in a receiving terminal, as compared to an export terminal
consisting of a liquefaction plant, and the hazards of fire and explosion
events with potential to affect the tank is not significant. Hence external
fire and explosion hazards causing damage to the tank is considered to be
negligible. In any case, the frequency of tank failure considered in Section 1.1.3 is considered
representative of all potential failure modes.
A full scope Safeguards and
Security Risk Assessment (SSRA) was conducted in
Given the sensitive and
confidential nature of the analysis and in order to protect public safety, the
complete SSRA report is available only on a need to know basis to GOHK and
CAPCO security personnel.
The team who prepared the
SSRA reviewed the history of terrorist events on LNG terminal facilities and
determined that there has never been a terrorist incident at any LNG terminal
or LNG carrier that has resulted in a death or injury to a member of the
public. The relative risk of a terrorist induced injury or fatality to the
public at a Hong Kong terminal was also compared to that for other terminals
around the world, including Asia, Europe and the
The Project was benchmarked
against other LNG facilities worldwide in the
Based on the benchmarking
comparison on the risk of terrorist threats, the Project was assessed to be at
a lower security risk threat level than the other LNG terminals, indicating
that the
The conclusion reached by
the SSRA team was that based on the overall low threat environment in Hong Kong
and the risk analysis of the worst-case scenario of an intentional act in
nature, their recommended risk mitigating measures would help to reduce the
scenarios associated risk to a level that is well within levels generally accepted by industry
globally, for either a Black Point or South Soko Island terminal. It was also concluded that whilst risk of a terrorist act
directed at both sites is extremely low, the consequence of a terrorist event
on the public would be greater for an incident at a Black Point terminal or
against an LNG carrier on portions of the marine transit route to Black Point
than for a South Soko terminal or its marine transit.
The SSRA team assessed the
consequences that would result from the terrorist induced scenarios evaluated.
Based on the available published studies, the team determined that the
consequences of these events did not exceed the worst case events evaluated in
the Terminal and Marine QRA studies.
Based
on a detailed review of the various failure modes along with the safeguards
provided, the failure frequency of the full containment LNG tank is taken to be
1x10-8 per tank-year. This failure frequency encompasses internal
and process causes of failure as well as any natural/external hazards.
External
hazards to the LNG storage tanks from aircraft were assessed to have a
frequency below 1 x 10-9 per year. Helicopter crashes have a small
but quantifiable frequency but the tanks are designed to withstand such impacts
and so there would be no consequences from such an event. Hence, failure of the
storage tanks due to helicopter impact was also excluded from the analysis.
Helicopter
impacts into the piping and process areas are a possible scenario, but the
frequency of occurrence is small compared to process risks. Helicopter crash scenarios
are therefore included in the generic frequencies.
[1] Baker, N., Creed, M.,
Stratification and Rollover in Gas Storage Tanks, Trans IChemE, Vol. 74, Part
B, 1996
[2] BS
7777: Flat-bottomed, vertical, cylindrical storage tanks for low temperature
service,
[3] Giribone, R., Claude,
J., Comparative Safety Assessment of Large LNG Storage Tanks, Eleventh
International Conference on LNG, 1995
[4] EN
1473: Installation and Equipment for Liquefied Natural Gas – Design of onshore installations,
[5] TNO,
Guidelines for Quantitative Risk Assessment (The Purple Book), Report CPR 18E,
The
[6] Rijnmond Public Authority, A Risk
Analysis of Six Potentially Hazardous Industrial Objects in the Rijnmond Area-
A Pilot Study, COVO, D. Reidel Publishing Co., Dordrecht, 1982.
[7]
[8] E&P Forum, E&P Forum QRA
Datasheet Directory, 15 October 1996.
[9] Davies,
T., Harding, A.B., McKay, I.P., Robinson, R.G.J., Wilkinson, A., Bund
Effectiveness in Preventing Escalation of Tank Farm Fires, Trans IChem E, Vol
74, Part B, May 1996.
[10] Christensen,
R.A. and Eilbert, R.F., Aboveground Storage Tank Survey, EL RN-623, Entropy
Limited,
[11] Batstone, R.J. and Tomi, D.T., Hazard Analysis in
Planning Industrial Developments, Loss
Prevention, 13, 7, 1980.
[12]
Canvey: a second report, HSE, 1991.
[13] Hazards Analysis of a Proposed LNG Import Terminal
in the Port of Long Beach, California, Quest Consultants Inc., Aug 2005.
[14] GCO, Review of earthquake data for the Hong Kong region, GCO Publication No. 1/91, Civil Engineering Services Dept., Hong Kong Government, 1991
[15] GEO,
Seismic hazard analysis of the
[16] Scott,
D.N., Pappin, J.W., Kwok, M.K.Y., Seismic Design of Buildings in Hong Kong,
Hong Kong Institution of Engineers, Transactions, Vol. 1, No. 2, p.37-50, 1994
[17] ASCE/SEI
43-05, Seismic design criteria for structures, systems, and components in
nuclear facilities, ASCE, 2005
[18] Personal communication on tank
capacity studies with Technigaz, 2003
[19] Eurocode 8: Design of
Structures for Earthquake Resistance, European Committee for Standardisation,
1998
[20] Mizuno, T., Wadano, Y.,
Terada, N., Tsunomura, T., Demonstrative Safety Assessment of LNG Storage
Facility Earthquake Resistance and Reinforcement of Crisis Management at LNG
Receiving Terminals, Twelfth International Conference on LNG, 1998
[21] www.hko.gov.hk
[22] Lee,
B. Y., Report of Hong Kong
in the International Tsunami Seminar in the Western Pacific Region,
International Tsunami Seminar in the Western Pacific Region,
[23] LNG Receiving Terminal Project -
Environmental Design Basis Report, Ove Arup & Partners, 2005.
[24] Byrne,
J. P., The Calculation of Aircraft Crash Risk in the
[25]
www.ntsb.gov/aviation/Table6.htm
[26] Annual Review of Aircraft Accident Data: U.S.
General Aviation, Calendar Year 2001, National Transport Safety Board.
[27] Spouge,
J., A guide to Quantitative Risk Assessment for Offshore Installations, CMPT,
1999.
[28]
www.gfs.gov.hk/perform.htm
[29] Aircraft
Crash Impact Analyses Demonstrate Nuclear Power Plant’s Structural Strength,
Nuclear Energy Institute, Dec 2002.