Contents
5 NOISE IMPACT
5.1 Legislation, Standards and Guidelines
5.3 Construction Airborne Noise Impact Assessment
5.4 Construction Groundborne Noise
Figure 5.1
Locations
of Representative Noise Sensitive Receivers and Assessment Point
Appendix 5.1
Photos of selected representative NSRs
Appendix 5.2
SWL of PME
Appendix 5.3
Plant Inventory
Appendix 5.4
Locations of work Fronts
Appendix 5.5
Notional Distances between work fronts and NSRs
Appendix 5.6
Unmitigated Construction Noise Impact
Appendix 5.7
Sketch of Typical Temporary Noise Barrier or Enclosure
Appendix 5.8
Mitigated Construction Noise Impact
5.1
Legislation, Standards and Guidelines
5.1.1
Construction Noise during
Non-restricted Hours
5.1.1.1
The Noise Control Ordinance (NCO) (Cap.
400) provides the statutory framework for noise control in Hong Kong. Assessment procedures and standards are set
out in the respective Technical Memoranda (TM) promulgated under the NCO. The following TMs are applicable to the
assessment and control of construction noise.
·
TM on Noise from Construction Work other than
Percussive Piling (TM-GW);
·
TM on Noise from Percussive Piling (TM-PP); and
·
TM on Noise on Construction Work in Designated
Areas (TM-DA).
5.1.1.2
To ensure a better environment, the
TM-EIAO promulgated under the Environmental Impact Assessment Ordinance (EIAO)
(Cap. 499) has imposed more stringent criteria. For construction, there is no
statutory limit on daytime construction noise under the NCO and related
TMs. Nevertheless, the TM-EIAO
stipulates noise standards of 65 – 75 dB(A) for
daytime construction activities, as shown in the table below.
Table 5.1 Noise Standards for Construction Activities
Uses |
Noise Standards [1],
Leq (30 mins)
dB(A) |
|
0700 to 1900 hours on any day not being a Sunday or general holiday |
1900 to 0700 hours or any time on Sundays or general holiday |
|
All domestic premises including temporary housing
accommodation |
75 |
(See
Note 2) |
Hotels and hostels |
75 |
|
Educational institutions including kindergartens,
nurseries and all others where unaided voice communication is required |
70 65
(During examinations) |
Notes:
[1] The above
standards apply to uses that rely on opened windows for ventilation.
[2] The criteria laid down in the relevant
technical memoranda under the NCO for designated areas and construction works
other than percussive piling may be used for planning purpose. A Construction Noise Permit (CNP) shall be
required for the carrying out construction work during the period.
5.1.2
Construction Noise during
Restricted Hours
5.1.2.1
The NCO also provides statutory
control on general construction works during restricted hours (ie 1900 to 0700 hours (of the next day) from Monday to
Saturday and at any time on Sundays or public holidays). The use of PME for construction works during
restricted hours would require a Construction Noise Permit (CNP). The TM-GW details the procedures adopted by
EPD for assessing such application. The
granting of a CNP is subject to conditions stated in the CNP and it may be
revoked at any time for failure to comply with the permit conditions.
5.1.2.2
In addition to the general
controls on the use of PME during restricted hours, the use of Specified
Powered Mechanical Equipment (SPME) and the undertaking of Prescribed
Construction Work (PCW) during the restricted hours in a designated area are
controlled by the TM-DA. Construction
plant or equipment classified as SPME under the TM-DA includes hand-held
breakers, bulldozers, concrete mixer lorries, dump
trucks and poker vibrators. The PCW includes the erection or dismantling of
formwork or scaffolding, hammering, handling of rubble, wooden boards, steel
bars, or scaffolding material, and the disposal of rubble through plastic
chutes.
5.1.2.3
The TM-DA details the
procedures that should generally be adopted by the Authority for assessing the
use of SPME during restricted hours and for determining whether a CNP would be
issued.
5.1.2.4
Maximum noise levels from
construction activities during restricted hours at affected NSRs are controlled
under the TMs and shall not exceed the specified Acceptable Noise Levels
(ANLs). These ANLs are stipulated in
accordance with the Area Sensitivity Ratings established for the NSRs. The ANLs for construction works in Designated
Areas are more stringent than those given in the GW-TM and summarized in the
table below.
Table 5.2 Acceptable Noise Levels for Construction during Restricted Hours
Time Period |
Acceptable Noise Levels for Area Sensitivity Ratings, dB(A) |
||
A |
B |
C |
|
All weekdays
during the evening (1900 to 2300 hours), and general holidays (including
Sundays) during the day and evening (0700 to 2300 hours) |
60 (45) |
65 (50) |
70 (55) |
All days during
the night-time (2300 to 0700 hours) |
45 (30) |
50 (35) |
55 (40) |
Note:
[1]
Figures in brackets are ANLs for SPME construction work in designated areas
Area Sensitivity Rating
5.1.2.5 The appropriate Area Sensitivity Rating for the NSR shall consider under consideration from below table.
5.1.2.6 Any NSR shall, irrespective of Table 5.3, be assigned an Area Sensitivity Rating of "C" if it is within 100 m of a zone designated as "Industrial" or "Industrial Estate" on a statutory Outline Zoning Plan, or an Area Sensitivity Rating of "B" if it is between 100 m and 250 m from such a zone, except in cases where Table 5.3 indicates an Area Sensitivity Rating of "C".
Table 5.3 Area Sensitivity Ratings
Type of Area containing
NSR |
Degree to which NSR is
affected by IF |
||
Not Affected |
Indirectly Affected |
Directly Affected |
|
(i) Rural area,
including country parks or village type developments |
A |
B |
B |
(ii) Low density residential area
consisting of low-rise or isolated high-rise developments |
A |
B |
C |
(iii) Urban area |
B |
C |
C |
(iv) Area other than those above |
B |
B |
C |
Note:
[1] For the purpose of Table 5.3, the following definitions apply:
"country park" means an area that is designated as a
country park pursuant to section 14 of the Country Parks Ordinance;
"directly affected" means that the NSR is at such a
location that noise generated by the IF is readily noticeable at the NSR and is
a dominant feature of the noise climate of the NSR;
"indirectly affected" means that the NSR is at such a
location that noise generated by the IF, whilst noticeable at the NSR, is not a
dominant feature of the noise climate of the NSR;
"not affected" means that the NSR is at such a location
that noise generated by the IF is not noticeable at the NSR; and
"urban area" means an area of high density, diverse
development including a mixture of such elements as industrial activities,
major trade or commercial activities and residential premises.
5.1.2.7 Despite any description made in this EIA, there is no guarantee that a CNP will be issued for the project construction. The Noise Control Authority will consider a well-justified CNP application, once filed, for construction works within restricted hours as guided by the relevant TMs issued under the NCO. The Noise Control Authority will take into account contemporary conditions / situations of adjoining land uses and any previous complaints against construction activities at the site before making a decision in granting a CNP. Nothing in the EIA report shall bind the Noise Control Authority in making a decision. If a CNP is to be issued, the Noise Control Authority shall include in it any conditions demand. Failure to comply with any such conditions will lead to cancellation of the CNP and prosecution under the NCO.
5.2.1.1
With
reference to Annex 13 of the TM-EIAO, NSRs could be, but not limited to:
residential uses including temporary housing; institutional uses including
educational institutions, hospitals, medical clinics, homes for the aged,
convalescent homes, places of public worship, libraries, courts of law,
performing arts centres, auditoria, amphitheatres; others such as hostels and
country parks.
5.2.1.2
The
existing NSRs are identified by means of topographic maps, aerial photos, land
status plans, S.16 / S.12a Town Planning Ordinance and site inspections. Planned / committed NSRs are identified by
making reference to relevant Outline Zoning Plans (OZP), Outline Development
Plans (ODP), Layout Plans and other published plans in relation to the Town
Planning Board.
Figure 5.1 shows the
assessment area for the construction noise impact assessment. This assessment
area includes areas within 300m from the boundary of the Project. All existing
NSRs are identified by shading within the assessment area.
5.2.1.3
Assessment
points of NSRs are selected (see
Appendix
5.1 for their photos) based on the criteria that one assessment point is
selected on the first layer in each street block and it is near work fronts of
the Project. Because the effect of distance attenuation is related to the
proximity of NSRs to work fronts, nearer NSRs would be the most affected NSRs
and therefore the assessment points would be representative for the noise
impact assessment purpose. Their locations are shown in
Figure 5.1 and their details including name of building, use,
number of floors are given in Table 5.4.
Table 5.4 List of assessments points of NSRs
Building
name |
Planned
/ Existing |
NSD
ID. |
Use |
Number
of floors |
Fook On House |
Existing |
N01 |
Residential |
6 |
Kin Shing Building |
Existing |
N02 |
Residential |
6 |
Siu Fung Building |
Existing |
N03 |
Residential |
6 |
Man Yip Building |
Existing |
N04 |
Residential |
8 |
Healey Building |
Existing |
N05 |
Residential |
24 |
Fung Yue Building |
Existing |
N06 |
Residential |
6 |
WRLPS (South) |
Planned |
N07 |
Residential |
19-29 |
CCC Chun Kwok Primary School |
Existing |
N08 |
Educational |
5 |
Village houses |
Existing |
N09 |
Residential |
2 |
Po Fai Building |
Existing |
N10 |
Residential |
6 |
Yuen Long Mansion |
Existing |
N11 |
Residential |
16 |
Wah Cheong Mansion |
Existing |
N12 |
Residential |
6 |
Happy House |
Existing |
N13 |
Residential |
6 |
Tse King House Stage 1 |
Existing |
N14 |
Residential |
6 |
Ho Shun Fuk Building |
Existing |
N15 |
Residential |
26 |
Ho Wang Building |
Existing |
N16 |
Residential |
12 |
On Ning Building |
Existing |
N17 |
Residential |
12 |
Caritas Yuen Long Chan Chun Ha Secondary
School |
Existing |
N18 |
Educational |
6 |
5.2.1.4
Tai
Kiu Development is not selected as an assessment
point because its construction programme is not available at the time of
preparing this report.
5.3
Construction Airborne Noise Impact
Assessment
5.3.1
Noise Sources
5.3.1.1 The latest construction methodology is described in Section 3.5. Based on the tentative construction methodology, the major construction works will include the following activities:
·
Site clearance activities;
·
Temporary erection;
·
Piling works;
·
Column and table top construction;
·
Superstructure and steelworks; and
·
Parapet Wall Construction, and Associated Landscape
and Streetscape Works.
5.3.1.2 These construction activities will be carried out with the use of PME including breakers, generators, piling rigs, backhoes, dump trucks, air compressors, mobile cranes, water pumps, concrete lorry mixers, concrete pumps, etc. Sound Power Level (SWL) for each PME is established according to TM-GW and other relevant information as appropriate.
5.3.2
Assessment Methodology
5.3.2.1
Construction
airborne noise assessment has been conducted based on the following procedures:
·
Determine the assessment area, and identify
representative NSRs that may be affected by the works;
·
Obtain the construction method and work sequence
for the construction period;
·
Obtain the plant items for each corresponding
construction work sequence;
·
Determine the sound power levels of the plant items
according to the information stated in the TM-GW or other recognized sources of
reference, where appropriate;
·
Calculate the correction factors based on the
distance between the NSRs and the notional noise source positions of the work
sites;
·
Apply corrections for façade, distance, barrier
attenuation, acoustic reflection where applicable;
·
Quantify the level of impact at the NSRs in
accordance with TM-GW;
·
For any exceedance of
noise criteria, all practical mitigation measures such as alternative
construction methodology, quiet plant, silencer, enclosure, etc. shall be
examined to alleviate the predicted noise impacts as much as practicable.
5.3.2.2
As
there is no concurrent project identified, the construction airborne noise
assessment focuses on the Project itself.
5.3.3
Utilization Rates and SWLs of
Powered Mechanical Equipment
5.3.3.1
Practically,
the PMEs will not be operating for all times within a work site. According to
“EIAO Guidance Note No. 9/2010”, a reasonable percentage on-time to reflect the
actual situation could be accepted as basic assumption for that kind of PMEs in
the assessment. The utilization rates will depend on the construction
sequences, work fronts scale and nature of construction. For example, (1) hand-held
breaker will only be used for breaking existing hard paving or existing nullah structure. It is expected that the breaker will be
stopped during removing the debris; (2) concrete lorry mixer and concrete pump
will only be used on the day of concreting. It is expected that the mixer and
pump will not continuously stay and operate on site. They will be removed after
pouring concrete; and, (3) for dump truck, it is understood that loading /
unloading is the main source of noise from and it is expected that the loading
/ unloading will not continuously operate on site.
5.3.3.2
In
this assessment, the utilization rates for each work front during different
periods have been reviewed by the engineer and have been concluded to be
practicable for the purpose of this EIA.
Appendix
5.2 summarizes the adopted utilization rates and the associated SWL for
different construction sequences.
Appendix
5.3 assesses the total SWL for different types of construction activities.
5.3.4
Noise Assessment Tool
5.3.4.1
An
in-house program has been used for construction noise assessment. Initially,
the program runs were conducted without any mitigation measures (i.e. the
“Unmitigated Scenario”). Where noise level exceedance
was identified, further runs will be made assuming different combinations of
mitigation measures to be incorporated (i.e. the “Mitigated Scenario”).
5.3.5
Assessment Results –
Unmitigated Scenarios
5.3.5.1
According
to the latest engineering design, the construction works will mainly comprise
of the activities as described in Section
5.3.1. The corresponding Sound Power Levels (SWLs) of these activities have
been assessed according to the PME’s SWLs and the assessment methodology in
GW-TM.
Appendix 5.4 shows the locations
of work fronts.
Appendix 5.5 presents
the distance between the notional sources and the NSRs.
Appendix 5.6 presents the unmitigated construction noise impacts at
selected representative NSRs. The predicted construction noise impacts on the
NSRs are summarized in Table 5.5
below.
Table 5.5 Predicted Maximum Unmitigated Construction Noise Levels at NSRs
NSR ID |
NSR Description |
Use |
Criterion dB(A) |
Unmitigated Noise Level[1] dB(A) |
Exceedance [1]
dB(A) |
N01 |
Fook On House |
R |
75 |
82 |
7 |
N02 |
Kin Shing Building |
R |
75 |
86 |
11 |
N03 |
Siu
Fung Building |
R |
75 |
86 |
11 |
N04 |
Man Yip
Building |
R |
75 |
86 |
11 |
N05 |
Healey
Building |
R |
75 |
84 |
9 |
N06 |
Fung
Yue Building |
R |
75 |
86 |
11 |
N07 |
West
Rail Long Ping Station (South) |
R |
75 |
79 |
4 |
N08 |
CCC
Chun Kwok Primary School |
E |
70 (65) |
80 (77) |
10 (12) |
N09 |
Village
houses |
R |
75 |
81 |
6 |
N10 |
Po Fai
Building |
R |
75 |
87 |
12 |
N11 |
Yuen
Long Mansion |
R |
75 |
85 |
10 |
N12 |
Wah Cheong Mansion |
R |
75 |
86 |
11 |
N13 |
Happy
House |
R |
75 |
85 |
10 |
N14 |
Tse
King House Stage 1 |
R |
75 |
81 |
6 |
N15 |
Ho Shun
Fuk Building |
R |
75 |
76 |
1 |
N16 |
Ho Wang
Building |
R |
75 |
78 |
3 |
N17 |
On Ning Building |
R |
75 |
74 |
- |
N18 |
Caritas Yuen Long Chan Chun Ha Secondary
School |
E |
70 (65) |
68 (68) |
- (3) |
Notes:
[1] Bolded
values mean exceedance of the relevant noise
criteria.
5.3.6
Mitigation Measures
5.3.6.1
The
predicted construction noise levels show that the unmitigated construction
noise impacts will exceed the daytime noise criteria at all the representative
NSRs except On Ning Building [N17]. Mitigation
measures are therefore required. The following mitigation measures have been
considered:
·
Use of quiet plants and working methods;
·
Use of shrouds / temporary noise barriers to screen
noise from relatively static PMEs; and
·
Alternative use of plant items within one worksite,
wherever practicable.
Use of quiet plants and
working methods and use of temporary noise barrier and enclosure (with
sufficient ventilation) are further described below:
Use of “Quiet” Plant and Working Methods
5.3.6.2 The use of quiet plant is a feasible solution to tackle adverse noise impacts associated with construction works. It is generally known (supported by field measurement) that particular models of construction equipment are quieter than standard types given in the TM-GW. Whilst it is generally considered too restrictive to specify that the Contractor has to use specific models or items of plant, it is reasonable and practicable to set plant noise performance specifications for specific PME so that some flexibility in selection of plant is allowed. A pragmatic approach would be to request that the Contractor independently verifies the noise level of the plant proposed to be used and demonstrates through furnishing of these results, that the plant proposed to be used on the site meets the requirements.
5.3.6.3 An inventory of SWLs of quiet plant associated with the construction works is given in EPD’s Quality Powered Mechanical Equipment (QPME) and additional reference is made to typical SWLs for international manufacturer. It should be also noted that while various types of silenced equipment could be found in Hong Kong, EPD when processing a CNP application for evening or night time works may apply the noise levels specified in the TM-GW and TM-DA. CNP applications which contain sufficient details of any particularly quiet items of PME or any special noise control measures which the CNP applicant proposes to employ on the site may be given special consideration by the Noise Control Authority.
5.3.6.4
A
summary of the “Quiet” PMEs adopted and the associated SWLs is given in
Appendix 5.2.
Use of Temporary Noise Barrier & Enclosure
(with Sufficient Ventilation)
5.3.6.5 Movable temporary noise barriers that can be located close to noisy plant and be moved concurrently with the plant along a worksite can be very effective for screening noise from NSRs. A typical design which has been used locally is a wooden framed barrier with a small-cantilevered on a skid footing with 25mm thick internal sound absorptive lining. This measure is particularly effective for low level zone of NSRs. A cantilevered top cover would be required to achieve screening benefits at upper floors of NSRs.
5.3.6.6 Movable barriers will be used for some PME (e.g. excavator, mobile crane, concrete lorry mixer, vibratory poker, etc.). It is anticipated that suitably designed barriers could achieve at least 5 - 10dB(A) reduction. For a conservative assessment, only a reduction of 5dB(A) is assumed. Acoustic mat will be used for other plant items including piling machines. A 10 dB(A) noise reduction is anticipated. Barrier material with surface mass at least 7kg/m2 is recommended to achieve the predicted screening effect. This assumption has been adopted in other approved EIA Reports.
5.3.6.7 The use of enclosure (with sufficient ventilation and surface mass at least 10 kg/m2) has been considered in this assessment to shelter relatively static plant. The enclosures barriers can provide about 10-15dB(A) noise reduction.
5.3.6.8 A summary of the temporary movable barriers and enclosures adopted for various PMEs, and the associated noise reduction is given in Appendix 5.2. Appendix 5.7 shows the sketch of typical temporary noise barrier / enclosure with air flow, allowing natural ventilation.
5.3.6.9 Regular site audit would be carried out during the construction for auditing the implementation of noise mitigation measures according to the EIA’s recommendation and EM&A requirements.
5.3.7
Assessment Results –
Mitigated Scenario
5.3.7.1
With
the implementation of the abovementioned mitigation measures, the construction
noise levels at the affected NSRs are predicted and presented in Table 5.6.
Appendix 5.8 presents the mitigated noise levels at selected
representative NSRs.
Table 5.6 Predicted Maximum mitigated Construction Noise Levels at NSRs
NSR ID |
NSR Description |
Use |
Criterion dB(A) |
Mitigated Noise Level dB(A) |
Exceedance
dB(A) |
N01 |
Fook On House |
R |
75 |
72 |
- |
N02 |
Kin Shing
Building |
R |
75 |
75 |
- |
N03 |
Siu Fung Building |
R |
75 |
75 |
- |
N04 |
Man Yip Building |
R |
75 |
75 |
- |
N05 |
Healey Building |
R |
75 |
74 |
- |
N06 |
Fung Yue Building |
R |
75 |
75 |
- |
N07 |
West Rail Long Ping Station (South) |
R |
75 |
70 |
- |
N08 |
CCC Chun Kwok Primary School [1][2] |
E |
70 (65) |
70 (68) |
- (3) |
N09 |
Village houses |
R |
75 |
73 |
- |
N10 |
Po Fai Building |
R |
75 |
75 |
- |
N11 |
Yuen Long Mansion |
R |
75 |
75 |
- |
N12 |
Wah Cheong Mansion |
R |
75 |
75 |
- |
N13 |
Happy House |
R |
75 |
74 |
- |
N14 |
Tse King House Stage 1 |
R |
75 |
71 |
- |
N15 |
Ho Shun Fuk
Building |
R |
75 |
68 |
- |
N16 |
Ho Wang Building |
R |
75 |
68 |
- |
N17 |
On Ning
Building |
R |
75 |
64 |
- |
N18 |
Caritas Yuen
Long Chan Chun Ha Secondary School [1] |
E |
70 (65) |
58 |
- |
Notes:
[1] Values in parentheses indicate the noise
criterion during examination period.
[2] Based on the best available information from
the school website about the examination periods over the school year of
2015/2016, it is assumed that the examination periods would remain the same in
the future and would be in October/November, January, March and June.
Scheduling of Construction Activities during
Examination Periods
5.3.7.2
The
predicted construction noise impacts on CCC Chun Kwok Primary School (NSR8) are
discussed for normal period and examination period respectively. According to
the best available information from the school website for the school year of
2015/2016, there are four examination periods in October/November, January,
March and June and each examination period would last for approximately one
week.
5.3.7.3
For
normal school periods in February, April, May, July, August, September and
December over the year, the predicted noise impacts range from 38dB(A) to
70dB(A) which would not exceed the criterion of 70dB(A) for normal school hours
throughout the construction period.
5.3.7.4
For
examination periods, each examination would last for approximately one week.
That is, there are typically four examination weeks in a year and 18
examination weeks over the planned construction activities for 53 months. The
predicted noise impacts in October/November, January, March and June ranges
between 51 and 68 dB (A). There are totally five examination weeks over the
whole planned construction activities which may have potential noise exceedance over 65 dB(A) (predicted noise impacts at 66 –
68 dB(A)) but this potential noise exceedance can be
avoided with the following arrangement:
·
The
contractor could daily liaise with the school management about the arrangements
during examination weeks.
·
Quieter
work activities can be arranged and noisy works, such as concrete operation and
operation of dump trucks should be avoided.
·
As
discussed in the Environmental and Audit Manual, a monitoring point (M01) is proposed
at the school. If noise exceedance is found in
monitoring during the examination weeks, construction works should be adjusted
and rearranged according to the Event and Action Plan listed in the EM&A
Manual.
5.3.7.5
With
the above arrangements in place, noise exceedance at
the school during examination weeks can be readily addressed.
5.3.8
Good Site Practice
5.3.8.1
In
addition to the mitigation measures suggested in Section 5.3.6, other good site
practices are useful to reduce noise impacts. For the purpose of conservative
assessment, the following good site practices have not been included in the
quantitative assessment as discussed in the following sections.
5.3.8.2
The
good site practices include:
·
only well-maintained plant should be operated
on-site and plant should be serviced regularly during the construction programme;
·
machines and plant (such as trucks, cranes) that may
be in intermittent use should be shut down between work periods or should be
throttled down to a minimum;
·
plant known to emit noise strongly in one
direction, where possible, be orientated so that the noise is directed away
from nearby NSRs;
·
silencers or mufflers on construction equipment
should be properly fitted and maintained during the construction works;
·
mobile plant should be sited as far away from NSRs
as possible and practicable;
·
material stockpiles, site office and other
structures should be effectively utilised, where
practicable, to screen noise from on-site construction activities; and,
·
Use of site hoarding to screen noise at ground
level of NSRs. Site hoarding (approximately 2.5m high) is located on the
site boundaries between construction activities and NSRs could generally reduce
noise levels through partial screening. Good site practice shall also be
adopted by the Contractor to ensure the conditions of the hoardings are
properly maintained throughout the construction period. For conservative assessments, however, the
site hoarding has not been taken into consideration in the construction noise
assessments.
5.3.8.3 The benefits of these techniques can vary according to specific site conditions and operations. The environmental noise climate would certainly be improved through these control practices, although the improvement can only be quantified during implementation when specific site parameters are known. The assessment has therefore not taken into account the effectiveness of the good site practices and noise management techniques.
5.4
Construction Groundborne Noise
5.4.1.1 As presented in Section 5.3.1, the Project does not involve drilling and blasting, or the use of Tunnel Boring Machine (TBM). Besides piling rigs would be used in the Project instead of percussive piling. Hence, it is anticipated that construction groundborne noise will not cause significant impact.
5.5.1.1 Construction airborne noise assessment has been conducted. All the practicable mitigation measures have been recommended to minimise the noise impacts. These mitigation measures include the optimisation of construction methodology (i.e. scheduling of PME uses, quiet plant, temporary noise barrier and good site practices). With the implementation of noise mitigation measures, no exceedance over relevant construction noise criteria is predicted at the representative noise sensitive receivers.
5.5.1.2 Because the Project does not involve drilling and blasting, or the use of TBM. It is anticipated that construction groundborne noise will not cause adverse impact.