Appendix 4.2  Construction Noise Impact Assessment
(F1)  Calculation of Construction Noise Levels at Representative Noise Sensitive Receivers - Mitigated (Quite Plant+Barrier)
NSR: "LUT"    
    SWL Distance B.C.* CNL       Cumulative Activities      
Activity   (dB(A)) (m) (dB(A)) (dB(A)) (I) (II) (III) (I)+(II) (I)+(III)A (I)+(III)B (I) + (III)C
(I) Water Mains Construction      
A Excavation of Trench / Breaking up Pavement 102 14 74 74 - - - - - -
B Installation of Pipes and Bedding 98 14 71 71 - - - - - -
C Backfilling 98 14 70 70 - - - - - -
D Reinstating Road Surface 99 14 71 71 - - - - - -
(II) Demolishment of Pui O Raw Water Pumping Station      
A General Site Clearance / Demolition Works 114 - - - - - - - - -
(III) Construction of Pui O Raw Water Pumping Station      
A Foundation 113 - - - - - - - - -
B Superstructural Works 112 - - - - - - - - -
C Installation of E&M Equipment and Commissioning & Testing 102 -   - - - - - - - -
NSR: "BOS" (During Normal Teaching Period)    
    SWL Distance B.C.* CNL       Cumulative Activities      
Activity   (dB(A)) (m) (dB(A)) (dB(A)) (I) (II) (III) (I)+(II) (I)+(III)A (I)+(III)B (I) + (III)C
(I) Water Mains Construction      
A Excavation of Trench / Breaking up Pavement 102 24 70 70 - - - - - -
B Installation of Pipes and Bedding 98 24 66 66 - - - - - -
C Backfilling 98 24 65 65 - - - - - -
D Reinstating Road Surface 99 24 66 66 - - - - - -
(II) Demolishment of Pui O Raw Water Pumping Station      
A General Site Clearance / Demolition Works 114 - - - - - - - - -
(III) Construction of Pui O Raw Water Pumping Station   - - - - -
A Foundation 113 - - - - - - - - -
B Superstructural Works 112 - - - - - - - - -
C Installation of E&M Equipment and Commissioning & Testing 102 -   - - - - - - - -
NSR: "LWT1"    
    SWL Distance B.C.* CNL       Cumulative Activities      
Activity   (dB(A)) (m) (dB(A)) (dB(A)) (I) (II) (III) (I)+(II) (I)+(III)A (I)+(III)B (I) + (III)C
(I) Water Mains Construction      
A Excavation of Trench / Breaking up Pavement 102 13 75 75 - - - - - -
B Installation of Pipes and Bedding 98 13 72 72 - - - - - -
C Backfilling 98 13 71 71 - - - - - -
D Reinstating Road Surface 99 13 72 72 - - - - - -
(II) Demolishment of Pui O Raw Water Pumping Station      
A General Site Clearance / Demolition Works 114 - - - - - - - - -
(III) Construction of Pui O Raw Water Pumping Station   - - - - -
A Foundation 113 - - - - - - - - -
B Superstructural Works 112 - - - - - - - - -
C Installation of E&M Equipment and Commissioning & Testing 102 -   - - - - - - - -
(F2)  Calculation of Construction Noise Levels at Representative Noise Sensitive Receiver BOS (during examination period)
       - Mitigated (Quite Plant+Barrier)
NSR: "BOS"      
    SWL Distance B.C.* CNL       Cumulative Activities      
Activity   (dB(A)) (m) (dB(A)) (dB(A)) (I) (II) (III) (I)+(II) (I)+(III)A (I)+(III)B (I) + (III)C
(I) Water Mains Construction      
A Excavation of Trench / Breaking up Pavement 97 24 64 64 - - - - - -
B Installation of Pipes and Bedding 97 24 64 64 - - - - - -
C Backfilling 98 24 65 65 - - - - - -
D Reinstating Road Surface 97 24 65 65 - - - - - -
(II) Demolishment of Pui O Raw Water Pumping Station      
A General Site Clearance / Demolition Works 114 - - - - - - - - -
(III) Construction of Pui O Raw Water Pumping Station   - - - - -
A Foundation 113 - - - - - - - - -
B Superstructural Works 112 - - - - - - - - -
C Installation of E&M Equipment and Commissioning & Testing 102 -   - - - - - - - -
List of Abbreviations:
SWL - Sound Power Level
CNL - Corrected Noise Level