4B.1 BPPS
Contribution
Since the BPPS is gas-fired gas
turbine power plant, the SO2 emission is very negligible in
accordance with the BPPS EIA Study, Annex
B (Source Emissions and Characteristics – Option 3). Therefore, in this Study, no SO2
concentration attributable to BPPS is considered.
4B.2 CPPS
Contribution
Short-term SO2
Concentration
For
the ASRs A3 to A8, the worst wind direction blowing from LNG Terminal to the
ASRs is opposite to the worst wind direction blowing from CPPS to the ASRs,
therefore, no short-term cumulative SO2 concentration is anticipated
at ASRs A3 to A8.
For ASRs A1
and A2 located at Sheung Pak Nai
and Nim Wan, respectively, contribution from CPPS is
likely to cause cumulative SO2 impact with the LNG Terminal
contribution.
The CPPS
contribution assessed in the BPPS EIA
Study is used in the following calculation.
In
the BPPS EIA Study, no wind tunnel testing was performed at Sheung
Pak Nai.
However, Sheung Pak Nai
(8 km) is located further away from CPPS than Nim
Wan/Ha Pak Nai (i.e., 5.5 km) and the NO2
concentration at Sheung Pak Nai
should be lower than that at Nim Wan/Ha Pak Nai. Therefore,
SO2 concentrations predicted at Nim Wan/Ha
Pak Nai are used as worst case SO2
concentration at Sheung Pak Nai.
The
worst wind direction of CPA and CPB to Nim Wan/Ha Pak
Nai is about 195°. However, no wind tunnel testing for SO2
was performed at such wind angle and hence the NOx
concentrations in the Annex H, Table H.1b
of the BPPS EIA Study, (maximum
hourly NOx concentration at 8 ms-1
are 118.3 µgm-3 and 91.7 µgm-3, contributed from CPA and
CPB, respectively), will be adjusted to SO2 concentrations by using
the ratio of existing SO2 licensed limit (i.e., 2,100 mgm-3)
and NOx concentrations in the BBPS EIA Study Annex B (Source Emissions and
Characteristics, i.e., 1577 mgm-3). Hence, the source SO2
concentrations are both 133% of source NOx
concentrations for CPA and CPB and the SO2 concentrations
attributable to CPA and CPB are, therefore, 157 µgm-3
and 122 µgm-3, respectively.
There
is no flue gas desulphurization system (FGD) applied to the current CPA and CPB
operation. For CPB, FGD will be
installed to reduce SO2 emission and about 89% of SO2
concentration will be reduced at Nim Wan/Ha Pak Nai area in accordance with the EIA for Emission Control Project to CPPS “B” Units, Annex A, Table A.4. Therefore, 89% SO2 reduction
will be applied to the adjusted SO2 concentration attributable to
CPB. Therefore, maximum hourly SO2
concentration attributable to CPB will be 122 µgm-3 x (1-0.89) = 13
µgm-3.
Therefore,
total maximum hourly SO2 concentration attributable to CPA and CPB is
157 + 13 = 170 µgm-3.
Long-term SO2
Concentration
The
2nd daily and annual average SO2 concentrations presented
in the BPPS EIA Study, Part B, Table 6.2b
had considered the contribution from CPPS (no contribution from BPPS as
negligible SO2 emissions due to gas-fired plant operation). Comparing the existing SO2
licence limit of 2,100 mgm-3 of both CPA and CPB and the source SO2
concentrations in the BPPS EIA Study,
Part B, Table 6.2b (1,635 mgm-3 for CPA and 1,726 mgm-3
for CPB), the 2nd daily and annual average SO2
concentrations in the BPPS EIA Study,
Part B, Table 6.2b are adjusted by applying a factor of 1.28 ([1]) to
reflect the current power station operation and the adjusted 2nd
daily and annual average SO2 concentrations are summarized as below.
|
Lung
Kwu Tan |
Ha
Pak Nai |
Worst
wind speed adopted in Wind Tunnel Testing (m/s) |
12 |
8 |
2nd
Highest Daily SO2 Concentration |
11% of AQO (39µgm-3) |
17 % of AQO (60 µgm-3) |
Annual
SO2 Concentration |
1 % of AQO (0.8 µgm-3) |
1.9 % of AQO (1.5 µgm-3) |
Note: (a)
Reference
to BPPS EIA Study, Part B, Table 6.2b
and a factor of 1.28 is applied. |
As
the above long-term SO2 concentrations are contributed from both CPA
and CPB and hence the SO2 emission from CPB will be adjusted by further
reduced due to the implementation of the Emission
Control Project to CPPS “B” Units.
In
the BPPS EIA Study, no wind tunnel testing was performed at Sheung
Pak Nai.
However, Sheung Pak Nai
(8 km) is located further away from CPPS than Nim Wan/Ha
Pak Nai (i.e., 5.5 km) and the NO2
concentration at Sheung Pak Nai
should be lower than that at Nim Wan/Ha Pak Nai. Therefore,
SO2 concentrations predicted at Nim Wan/Ha
Pak Nai are used as worst case SO2
concentration at Sheung Pak Nai.
Summary
A summary of
adjusted short-term and long-term SO2 concentrations are presented
as below.
|
Lung
Kwu Tan |
Nim Wan / Ha Pak Nai |
Sheung Pak Nai
(a) |
Worst
wind speed adopted in Wind Tunnel Testing (m/s) |
12 |
8 |
8 |
Adjusted
Maximum Hourly SO2 Concentration |
- |
170 µgm-3 (b) (CPPS ONLY) |
170 µgm-3 (b) (CPPS ONLY) |
Adjusted
2nd Highest Daily SO2 Concentration |
39 µgm-3 |
60 µgm-3 |
60 µgm-3 |
Adjusted
Annual SO2 Concentration |
0.8 µgm-3 |
1.5 µgm-3 |
1.5 µgm-3 |
Note: (a)
No
wind tunnel testing was performed at Sheung Pak Nai in the BPPS EIA Study; the SO2
concentrations predicted at Nim Wan/Ha Pak Nai is used as worst case assumption. (b)
A
total SO2 concentrations of CPA and CPB contributions (i.e., 157
µgm-3 + 13 µgm-3 = 170 µgm-3) |
For
the worst case assessment, the adjusted 2nd highest daily and annual
average SO2 concentrations at Nim Wan/Ha
Pak Nai (60 mgm-3 and
1.5 mgm-3,
respectively) will be adopted for the cumulative long-term impact assessment at
all identified ASRs and for plotting the contours to assess the worst case
cumulative SO2 impacts.
Of
note, in accordance with the indicative commencement programme in the Emission Control Project to CPPS “B” Units,
the FGD will be operated in end of 2009 to 2011 which should be earlier than
the LNG Terminal operation.
Therefore, during the LNG Terminal operation, the 2nd highest
daily and annual average SO2 concentration should be much lower
based on the future SO2 reduction programme at CPB.
Similar
to short-term NO2 contribution from CPPS, no contribution of SO2
from CPPS to Nim Wan/Ha Pak Nai
and Sheung Pak Nai areas at
232°
(which is the same worst wind angle of LNG terminal to Nim
Wan/Ha Pak Nai and Sheung
Pak Nai areas.
Therefore, the cumulative short-term SO2 impact considering
the SO2 contribution from CPPS at 195° is
a very worst case assessment in this study.
Therefore, the cumulative short-term and long-term SO2
impact assessment in this Study will be the worst-case assessment.