5                    NOISE IMPACT ASSESSMENT

 

5.1              Introduction

 

5.1.1         This Section provides an evaluation of the potential noise impacts arising from the construction and operation of the proposed Project.  Appropriate mitigation measures will be recommended, where necessary, in order to mitigate any unacceptable impacts.

 

5.2              Environmental Legislation, Policies, Standards and Criteria

 

Construction Phase

 

5.2.1         The principal legislation relating to the control of construction noise is the Environmental Impact Assessment Ordinance (Cap. 499).  The Technical Memorandum on Environmental Impact Assessment Process (EIAO-TM), issued under the EIAO, provides guidelines and noise criteria for evaluating noise impacts.  The assessment criteria are defined in Annex 5 of the EIAO-TM.

 

5.2.2         The Noise Control Ordinance (NCO) (Cap. 400) also provides means to assess construction noise impacts.  A number of Technical Memoranda (TMs) have been issued under the NCO to stipulate control approaches and criteria.  The Technical Memorandum on Noise from Construction Work Other than Percussive Piling (GW-TM) provides the guidelines for controlling the construction noise from powered mechanical equipment (PME) in general construction works during the restricted hours. The Technical Memorandum on Noise from Construction Works in Designated Areas (DA-TM) provides the guidelines for controlling the use of Specified Powered Mechanical Equipment (SPME) and the undertaking of Prescribed Construction Work (PCW) during the restricted hours in a designated area.

 

General Construction Works during Normal Working Hours

 

5.2.3         Under the EIAO, potential noise impact arising from general construction works during normal working hours (i.e. 0700 to 1900 hrs on any day not being a Sunday or general holiday) at 1 m from the external façade of the noise sensitive uses, which rely on opened windows for ventilation, is to be assessed in accordance with the noise criteria specified in the EIAO-TM.  The EIAO-TM noise standards are presented in Table 5.1.


Table 5.1         EIAO-TM Day-time Construction Noise Standards

Noise Sensitive Uses

Noise Standard

0700 to 1900 hours on any day not being a Sunday or general holiday

Leq, 30 min (dB(A))

·         All domestics premises including temporary housing accommodation

75

·         Hotels and hostels

75

·         Educational Institutions including kindergartens, nurseries and all others where unaided voice communication is required

70

65

(During examinations)

Notes:

(1)  The above standards apply to uses which rely on opened windows for ventilation.

(2)  The above standards shall be viewed as the maximum permissible noise levels assessed at 1m from the external façade.

 

General Construction Works during Restricted Hours

 

5.2.4         The NCO provides statutory controls on general construction works during restricted hours (i.e. 1900 to 0700 hours or any time on Sundays or general holidays).  The use of PME for carrying out construction works during these restricted hours would require a Construction Noise Permit (CNP).  The Noise Control Authority will assess all CNP applications on a case-by-case basis and, in doing so the authority advises that they will be guided by the GW-TM.

 

5.2.5         When assessing an application for CNP for the use of PME during restricted hours, the Noise Control Authority will compare the Acceptable Noise Levels (ANLs) specified in the GW-TM with the Corrected Noise Levels (CNLs) (i.e. after accounting for factors such as barrier effects and reflections) associated with the proposed PME operations.  The NCO requires that noise levels from construction at affected Noise Sensitive Receiver (NSR) be less than the specified ANL.  The ANLs are related to the inherent noise sensitivity of the noise receiver areas in question, and different Area Sensitivity Ratings (ASRs, i.e. A, B or C, see Table 5.2) have been established to reflect the background characteristics of different areas.  Each noise receiver area is assigned an ASR based on its predominant land use and the presence, if any, of Influencing Factors (IFs) such as nearby industrial areas, major roads or airports.  The appropriate ASR for the NSR is determined with reference to Table 5.2.


Table 5.2         Area Sensitivity Ratings

Types of Area Containing NSR

Degree to which NSR is affected by Influencing Factor (IF)

Not Affected

Indirectly Affected

Directly Affected

Rural area, including Country Parks or village type developments

A

B

B

Low density residential area consisting of low-rise or isolated high-rise developments

A

B

C

Urban area

B

C

C

Area other than those above

B

B

C

Notes:

The following definitions apply:

(a)       "Country Park" means an area that is designated as a country park pursuant to section 14 of the Country Parks Ordinance;

(b)       "directly affected" means that the NSR is at such a location that noise generated by the IF is readily noticeable at the NSR and is a dominant feature of the noise climate of the NSR;

(c)       "indirectly affected" means that the NSR is at such a location that noise generated by the IF, whilst noticeable at the NSR, is not a dominant feature of the noise climate of the NSR;

(d)       "not affected" means that the NSR is at such a location that noise generated by the IF is not noticeable at the NSR; and

(e)       "urban area" means an area of high density, diverse development including a mixture of such elements as industrial activities, major trade or commercial activities and residential premises.

 

5.2.6         The relevant ANLs for each ASR are shown in Table 5.3.

 

Table 5.3         Acceptable Noise Levels (ANLs) for General Construction Works to be carried out during Restricted Hours (GW-TM)

Time period

Area Sensitivity Rating

Leq, 5 min (dB(A))

 

A

B

C

All days during the evening (i.e. 1900-2300 hrs) and general holidays (including Sundays) during the day and evening (i.e. 0700-2300 hrs)

60

65

70

All days during the night-time (i.e. 2300-0700 hrs)

45

50

55

Note:

(a) The above standard applies to uses which rely on opened windows for ventilation.

 

5.2.7         The Noise Control Authority will consider a well-justified CNP application for construction works within restricted hours as guided by the relevant Technical Memorandum issued under the NCO.  The Noise Control Authority will take into account adjoining land uses and any previous complaints against construction activities at the site before making a decision.  Factors influencing the outcome of a CNP application, such as the assigning of ANLs, would be determined by the Noise Control Authority at the time of the application review based on the prevailing site conditions which may change from time to time.

 

5.2.8         The DA-TM issued under the NCO indicates a list of SPME and the types of PCW to be regulated within restricted hours in Designated Areas (DAs).  Under the DA-TM, the use of five types of SPME and the carrying out of three types of PCW within a designated area during restricted hours would require a valid CNP.  The SPME includes hand-held breaker, bulldozer, concrete lorry mixer, dump truck and hand-held vibratory poker.  The PCW are:

·                     Erecting or dismantling of formwork or scaffolding;

·                     Loading, unloading or handling of rubble, wooden boards, steel bars, wood or scaffolding material; and

·                     Hammering.

 

5.2.9         Part of the Project Site (i.e. the southern section from the Long Ping Station) falls within the designated area under the NCO. Hand-held breaker and concrete lorry mixer specified as SPME will be used during the construction and the use of these SPME during the restricted hours within the designated area shall be controlled by the TM-DA. The Noise Control Authority will assess the CNP applications based on procedures and requirements as described in the DA-TM.  In general, it should not be presumed that a CNP would be granted for the carrying out of PCW within a designated area during the restricted hours.  The CNP may be granted for the execution of construction works within a designated area during restricted hours involving the use of SPME if the relevant ANL and criteria stipulated in the DA-TM can be satisfied. In the EIA stage, no use of SPME is proposed for the construction works within the designated area during the restricted hours.

 

Operation Phase

 

5.2.10     Fixed plant noise associated with the operation of a project is controlled under Section 13 of the NCO, and the Technical Memorandum for the Assessment of Noise from Places Other than Domestic Premises, Public Places or Construction Sites (IND-TM).

 

5.2.11     The noise criteria, in terms of ANLs, stipulated in the IND-TM apply for all days and general holidays.  The ANLs are dependent on the ASR of the NSRs and the time of the day and are presented in Table 5.4. 


Table 5.4         ANLs for Fixed Noise Source under NCO

Time Period

Leq 30min (dB(A))

ASR “A”

ASR “B”

ASR “C”

Day-time (0700 - 1900 hrs)

60

65

70

Evening (1900 - 2300 hrs)

60

65

70

Night-time (2300 - 0700 hrs)

50

55

60

 

5.2.12     In accordance with the IND-TM, any NSR shall be assigned an ASR of “C” if it is within 100m of a zone designated as “Industrial” or “Industrial Estate” on a statutory Outline Zoning Plan, or an ASR of “B” if it is between 100m and 250m from such a zone. For conservative assessment, the NSR shall be assigned an ASR of “A” if it is outside the 250m from the zone and within the 300m assessment area.

 

5.2.13     For the purpose of EIA, fixed plant noise associated with the operation of a project is controlled under the EIAO.  The noise standards are set out in the Annex 5 of EIAO-TM as follows:

 

·           The total fixed source noise level at the façade of the nearest NSR is at least 5 dB(A) lower than the appropriate ANL (as shown in Table 5.4) as specified in the IND-TM; or

·           Where the prevailing noise level in the area is 5 dB(A) or more below the appropriate ANL, the total fixed source noise level must not exceed this noise level.

 

5.2.14     According to the approved Yuen Long Outline Zoning Plan (OZP) No. S/YL/23, the proposed DWF pumping station is located within a “Residential (Group E)1” (“R(E)1”) zone.  Assessment point, NSR3, was included in the operational noise impact assessment to represent the nearest NSR to the proposed DWF pumping station within 250m distance from the boundary of the Yuen Long Industrial Estate, zoned as “Other Specified Uses” annotated “Industrial Estate” (“OU(IE)”) in the OZP.  Representative NSRs that may potentially be affected by the operation of the proposed DWF pumping station are shown in Figure 5.2.

 

5.2.15     As the proposed DWF pumping station will operate 24 hours a day, the ANL-5 during night-time, for which is most stringent, will be adopted. With reference to the baseline noise level described in Section 5.3.2, the noise criteria of the fixed plant noise under EIAO for NSRs with different ASRs are presented in Table 5.5.


Table 5.5         Noise Criteria for Fixed Plant Noise under EIAO

ASR

ANL-5, dB(A)

 

Baseline Noise Levels, dB(A)

Fixed Plant Noise Criteria, dB(A)

A

45

 

48

45

B

50

 

48

48

C

55

 

48

48

 

5.2.16     In any event, the noise criterion employed in this Report is for an indicative operational noise assessment only.  It should be noted that fixed noise sources are controlled under Section 13 of the NCO.  At the time of investigation, the Noise Control Authority shall determine noise impact from concerned fixed noise sources on the basis of prevailing legislation and practices being in force, and taking account of contemporary conditions / situations of adjoining land uses.  Nothing in this Report shall bind the Noise Control Authority in the context of law enforcement against any fixed noise source being assessed.

 

 

5.3              Baseline Conditions

 

5.3.1         The existing ambient noise levels are mainly generated by traffic along Castle Peak Road, Yuen Long Highway, West Rail Line between Long Ping and Yuen Long and other local roads.  Background noise sources also include existing processing plants and factories located in the nearby Yuen Long Industrial Estate (YLIE) and Tung Tau Industrial Area (TTIA).

 

5.3.2         Background noise measurements to investigate the prevailing noise levels at the representative NSR near the proposed DWF pumping station have been undertaken from 17 January 2019 to 18 January 2019.  The measurement location is indicated in Figure 5.2.  The measured minimum background noise level during night-time period is lower than that of the ANL-5 levels for ASR B. The measured background noise levels are summarized in Table 5.6. The detailed baseline noise measurement data and record are provided in Annex 5A.

 

Table 5.6         Measured Baseline Noise Levels

Measurement Location

Time Periods

 

Measured Noise Levels, Leq, 30min dB(A)*

Shan Pui Chung Hau Tsuen

Day-time: 

07:00 to 23:00 hrs

55 – 65

 

Night-time:

23:00 to 07:00 hrs

48 - 59

            Note: *All extraneous noise data was neglected for determination of baseline noise level.


5.4              Noise Sensitive Receivers

 

5.4.1         Representative noise sensitive receivers (NSRs) were identified according to the criteria set out in the EIAO-TM. In accordance with the requirements stated in Clause 3.4.2.2 of the EIA Study Brief, the Study Area for the noise impact assessment covered an area of 300 m from the boundary of the Project Site. Only the first layer of NSRs has been identified for assessment as it would provide acoustic shielding to those receivers at further distance behind.

 

5.4.2         The 300 m study area is within the Yuen Long OZP No. S/YL/23 and Nam Sang Wai OZP No. S/YL-NSW/8. The relevant OZPs, Outline Development Plans and Layout Plans and the land use and development applications approved by the Town Planning Board have been reviewed. Site survey has also been conducted for identifying NSRs. A total of 25 existing and one planned representative NSRs have been identified based on the site survey and review of the land use plans. The identified representative NSRs are shown in Table 5.7 and their locations are indicated in Figure 5.1 a–d. The photos of the representative NSRs are presented in Annex 5B. In order to assess the worst-case scenario, the lowest floor of the NSRs have been selected as the assessment point.


Table 5.7         Representative Noise Sensitive Receivers (NSRs)

NSR ID

Description

Type of Usage

No. of Floors

Floor of selected assessment point

Horizontal Distance to the Nearest Site Boundary (m)

NSR01

Tung Tau Wai San Tsuen

Residential

2 – 3

G

12

NSR02

Shan Pui Chung Hau Tsuen

Residential

1 – 2

G

10

NSR03

Twin Regency

Residential

22

G

8

NSR04

Yuk Yat Garden

Residential

3

G

21

NSR05

Wang Fu Court

Residential

13

G

5

NSR06

Yeung Uk San Tsuen

Residential

3

G

28

NSR07

Yuen Long Long Ping Estate Wai Chow School

School

6

G

39

NSR08

The Spectra

Residential

25

G

11

NSR09

Tai Kiu Tsuen

Residential

1 – 4

G

8

NSR10

Fuk Yip Building

Residential

5

G

1

NSR11

Yuen Fat House

Residential

5

G

1

NSR12

Healey Building

Residential

24

G

2

NSR13

Wah Shing Mansion

Residential

5

G

6

NSR14

CCC Chun Kwong Primary School

School

5

G

1

NSR15

Tse King House

Residential

6

G

2

NSR16

On Ning Building

Residential

11

G

1

NSR17

Ho Wang Building

Residential

20

G

1

NSR18

Caritas Yuen Long Chan Chun Ha Secondary School

School

6

G

4

NSR19

Sun Fai Court

Residential

2 – 3

G

2

NSR20

Ma Tin Tsuen - Kung Um Road

Residential

3

G

2

NSR21

Yuen Long Villa

Residential

3

G

3

NSR22

Lung Tin Tsuen

Residential

3

G

31

NSR23

Wang Chau Lam Uk Tsuen

Residential

3

G

38

NSR24

Wang Chau Tung Tau Wai

Residential

3

G

64

NSR25

Hong Kong School of Motoring - Yuen Long Road Safety Centre

School

1

G

188

R1

Sol City (Planned)

Residential

19 – 29

G

8


5.5              Potential Sources of Impacts

Construction Phase

 

5.5.1         The Project includes the construction of the DWF interceptors and u-channels/pipes, DWF pumping station, and rising mains.  The major construction activities for the above works will include ground breaking, excavation, pipe laying, backfilling works and final re-instatement by in-situ concreting.  Potential sources of noise impacts during the construction phase of the Project will mainly arise from powered mechanical equipment (PME) operating at the construction work sites.  Based on the current construction design, percussive piling and blasting are not required. The details of project construction are given in Section 2.3.

 

5.5.2         Based on the current programme, no construction works will be required during the restricted hours under the NCO.  The normal working hours of the construction of the Project will be between 0700 and 1900 hours from Monday to Saturday (except general holidays).  Should evening and night works between 1900 and 0700 hours or on public holidays (including Sundays) be required, the Contractor will submit a CNP application which will be assessed by the Noise Control Authority.

Operation Phase

 

5.5.3         During the operation phase, only minor maintenance works such as regular clearance of debris inside the YLTN and repair of damages to the channel bed and sides are expected.  Thus, it is anticipated that the potential noise impacts arising from these maintenance works would be minimal.

 

5.5.4         Noise will be generated from fixed plant sources during operation, i.e. the DWF pumping station proposed to be located near the Yuen Long Kau Hui Sewage Pumping Station.  All equipment will be accommodated inside the plant rooms and hence fully enclosed.  Operational noise from the pumping station is assumed to be emitted through the louvres.  The fixed plant items for the proposed DWF pumping station is given below which have been agreed with the project proponent and relevant DSD divisions:

 

DWF pumping station:

·                     2 nos. of mechanical screens;

·                     2 nos. of submersible pumps; and

·                     2 nos. of exhaust fans (1 for deodourizer and 1 for general ventilation).

 

5.5.5         In addition to the above, extra set of mechanical screen, submersible pump and fan for ventilation will be provided as standby.  As they will only be operated when normal operating items are not working, the maximum no. of items in operation will be 2 nos. of each item.

 

5.6              Assessment Methodology

Construction Phase

 

5.6.1         The construction noise impact assessment was undertaken in accordance with the EIAO-TM and the procedures outlined in the GW-TM issued under the NCO.  The assessment methodology is summarised as follows:

·                     Identify the representative NSRs that may be affected by the construction of the Project;

·                     Determine the plant items for corresponding construction activities, based on the agreed plant inventory;

·                     Assign sound power levels (SWLs) to the PME proposed based on the GW-TM and list of SWLs of other commonly used PME([1]);

·                     Calculate the correction factors based on the distance between the NSRs and the notional noise source positions of different works areas;

·                     Apply corrections in the calculations, such as potential screening effects and acoustic reflection, if any; and

·                     Predict the construction noise levels at NSRs in the absence of any mitigation measures.

 

5.6.2         The construction noise assessment was undertaken based on the proposed construction works programme and plant inventory, and appropriate utilisation rates of the PME items (Annex 5C).  Same utilization rates have been used for the same type of PME among all works areas. The plant inventory (including the type of equipment, their quantity and utilization rate) in Annex 5C-2 have been reviewed by the Project Engineer and confirmed to be appropriate and practicable for completing the works within the proposed construction programme.

 

5.6.3         The proposed methods for the construction of the Project are common in Hong Kong and the PMEs proposed are available in the Hong Kong market.

 

5.6.4         For the purpose of the construction noise assessment, the entire construction site was divided into nine separate works areas (one for rising main, one for DWF pumping station, seven for DWFI system), with each works area expected to be operated for 5 to 14 months as shown in the construction programme in Annex 5C-1.  The nine separate works areas are presented in Figure 5.1a-e. 

 

5.6.5         The total SWL associated with each construction activity for the corresponding works areas was established.  The potential noise impacts at NSRs were subsequently evaluated by comparing the predicted noise levels with the EIAO-TM day-time construction noise limits (Leq, 30min dB(A)).

Operation Phase

 

5.6.6         The methodology for the fixed plant noise impact assessment follows the procedures outlined in the IND-TM.  The methodology is summarised as follows:

·                     Identify types of equipment and the number of equipment (if available);

·                     Assign sound power levels (SWLs) to the proposed equipment with reference to EIA studies in similar nature, noise data from supplier, Good Practices on Pumping System Noise Control (GP-PS) and Good Practices on Ventilation System Noise Control (GP-VS);

·                     Identify representative NSRs that may be affected by the fixed plant;

·                     Calculate the correction factors, using a conservative approach, based on the horizontal distance between the NSRs and the fixed plant sources;

·                     Calculate the corrected noise levels after taking into account other corrections such as potential screening effects, if any, by adopting standard acoustics principles; and

·                     Present the results in terms of Leq, 30min dB(A), as specified in the IND-TM.

 

5.6.7         The DWF pumping station will operate 24 hours a day as confirmed by the project proponent. A flow meter with automatic metering is required to ensure that the total flow through the pipe will not exceed the design capacity of 18,000m3/day. Once the total flow exceeds 18,000m3/day, the system will shut down the inlet penstock to avoid overloading of YLSTW. The operation of the proposed DWF pumping station have been commented and agreed with the project proponent and relevant DSD divisions in the submission of Design Memorandum.

 

5.6.8         Distance attenuation was taken into account in the noise calculations where the direct distance between the nearest louvre and each of the representative NSRs in the vicinity was estimated.  All the mechanical screens and submersible pumps will be totally enclosed inside building structure.  The exhaust fans will be fitted with acoustic louvre/silencer.  Barrier correction was also considered in which a noise reduction of 10 dB(A) was applied to the fixed plant depending on the line of sight of the representative NSRs.  A positive 3 dB(A) correction was included in the calculations to predict the noise levels at the NSRs due to façade effect. In the Environmental Review Report for application of Variation of Environmental Permit (VEP) for Yuen Long Kau Hui No. 2 Sewage Pumping Station with Environmental Permit (VEP-455/2014), the tonality correction of 0–3 dB(A) for four existing pumping stations nearby has been derived based on noise measurement. With reference to the report, a positive 3 dB(A) tonality correction was included in the noise calculation for the DWF pumping station.

 

5.6.9         No corrections have been applied for intermittency or impulsiveness as such noise characteristics are not expected.  If the noise shows any of these characteristics during the operation of the plant, the noise limit should be reduced in accordance with the recommendation indicated in Section 3.3 of IND-TM.

Level of Uncertainty

 

5.6.10     There would be some limitations such as the accuracy of the prediction for future conditions (e.g. plant inventory for the proposed construction works and fixed plant for future operation).

 

5.6.11     During the assessment, realistic worst-case assumptions have been made in order to provide a conservative assessment of noise impacts.  The construction noise impact was assessed based on conservative estimates for the types of plant and methods of working. For operation noise assessment, being the worst-case scenario, all items of equipment have been assumed to operate simultaneously during the operation period. For determining the distance correction factors, the horizontal distances between the noise source positions and the NSRs were used for representing the worst level of the representative NSRs for both construction and operation phases.

 

5.7              Impact Assessment

Construction Phase

 

5.7.1         The predicted façade noise levels during daytime period due to the construction activities are calculated in accordance with the methodology described in GW-TM.  The results are summarised in Table 5.8 with details of the noise calculations given in Annex 5C-2. 


Table 5.8         Predicted Construction Noise Levels (Without Mitigation Measures)

NSR No.

Description

Predicted Noise Level, dB(A)

Noise Criteria, Leq, 30min, dB(A)

NSR01

Tung Tau Wai San Tsuen

79

75

NSR02

Shan Pui Chung Hau Tsuen

82

75

NSR03

Twin Regency

89

75

NSR04

Yuk Yat Garden

75

75

NSR05

Wang Fu Court

75

75

NSR06

Yeung Uk San Tsuen

76

75

NSR07

Yuen Long Long Ping Estate Wai Chow School

72

70/65 (a)

NSR08

The Spectra

77

75

NSR09

Tai Kiu Tsuen

86

75

NSR10

Fuk Yip Building

89

75

NSR11

Yuen Fat House

89

75

NSR12

Healey Building

83

75

NSR13

Wah Shing Mansion

85

75

NSR14

CCC Chun Kwong Primary School

85

70/65 (a)

NSR15

Tse King House

80

75

NSR16

On Ning Building

82

75

NSR17

Ho Wang Building

89

75

NSR18

Caritas Yuen Long Chan Chun Ha Secondary School

80

70/65 (a)

NSR19

Sun Fai Court

89

75

NSR20

Ma Tin Tsuen - Kung Um Road

87

75

NSR21

Yuen Long Villa

88

75

NSR22

Lung Tin Tsuen

73

75

NSR23

Wang Chau Lam Uk Tsuen

76

75

NSR24

Wang Chau Tung Tau Wai

74

75

NSR25

Hong Kong School of Motoring - Yuen Long Road Safety Centre

66

70/65 (a)

R1

Sol City (Planned)

85

75

Notes:

(a)     70/65 denotes noise criteria during normal school days / examination period, respectively.

 

5.7.2         Results indicate that the construction noise levels at most of the representative NSRs exceeded the EIAO-TM noise criteria in day-time during the course of the construction period.  Therefore, mitigation measures will be required. 

            Operation Phase

 

5.7.3         The predicted fixed plant noise levels at the representative NSRs due to the operation of the proposed DWF pumping station are summarised in Table 5.9.  The predicted noise levels at all the representative NSRs comply with the noise criteria under EIAO as shown in Section 5.2.15.  Details of the calculation are given in Annex 5C-3.

 

Table 5.9         Predicted Fixed Plant Noise Levels due to the Proposed DWF Pumping Station

NSR

Description

Predicted Fixed Plant Noise Level, dB(A)

ASR

Applicable Noise Limit, dB(A)

Exceedance

NSR01

Tung Tau Wai San Tsuen

33

B

48

No exceedance

NSR02

Shan Pui Chung Hau Tsuen

33

B

48

No exceedance

NSR03

Twin Regency

45

B

48

No exceedance

NSR04

Yuk Yat Garden

27

A

45

No exceedance

NSR05

Wang Fu Court

27

A

45

No exceedance

NSR23

Wang Chau Lam Uk Tsuen

31

A

45

No exceedance

NSR24

Wang Chau Tung Tau Wai

30

B

48

No exceedance

 

5.7.4         The operation noise of the proposed DWF pumping station alone shall comply with the criteria under the EIAO. The specified SWLs presented in Annex 5C-3 should be included in the tender specification.  The suppliers of equipment should guarantee the compliance of EIAO-TM noise criteria, with the characteristics of tonality, impulsiveness and intermittency accounted for, by providing certificate of measurement and verify the SWL during testing and commissioning in accordance with international standard procedures.  If necessary, the suppliers should apply attenuation measures (e.g. use of silencers) to achieve the guaranteed noise levels during the detailed design stage.

 

5.8              Mitigation Measures

Construction Phase

 

5.8.1         In view of the predicted noise exceedances during the construction of the Project, the following mitigation measures have been considered:

 

·                     Good construction site practice;

·                     Use of quiet PME;

·                     Adoption of movable noise barriers;

·                     Use of noise insulation sheet;

·                     Adoption of fixed temporary noise barriers; and

·                     Scheduling of PME / construction activities.

      

       Good Construction Site Practice

 

5.8.2         Good construction site practice and noise management can considerably reduce the potential noise impact of the construction activities on nearby NSRs.  The noise benefits of these practices can vary according to specific site conditions and operations.  Since the effect of the good construction site practices could not be quantified, the mitigated noise levels calculated in the subsequent sections have not taken account of this effect.  The following site practices should be followed during the construction of the Project:

·                     Only well-maintained plant should be operated on-site and plant should be serviced regularly during the construction phase;

·                     Silencers or mufflers on construction equipment should be utilised and should be properly maintained during the construction phase;

·                     Mobile plant, if any, should be sited as far away from NSRs as possible;

·                     Machines and plant (such as trucks) that may be in intermittent use should be shut down between work periods or should be throttled down to a minimum;

·                     Plant known to emit noise strongly in one direction should, wherever possible, be orientated so that the noise is directed away from the nearby NSRs; and

·                     Material stockpiles and other structures should be effectively utilised, wherever practicable, in screening noise from on-site construction activities.

 

Use of Quiet PME

 

5.8.3         The use of quiet PME is considered to be a practicable means to mitigate the construction noise impact.  Quiet PME is defined as a PME having actual SWL lower than the value specified in the GW-TM.  The total SWL of all plant items to be used on-site at each works area will be specified so that flexibility is allowed for the Contractor to select plant items to suit the construction needs. The Contractor shall select plant items with total SWL equal to or lower than the total SWL specified in the plant inventory in Annex 5C-7 in order to meet the relevant noise criteria. Quiet PME that have been adopted in the assessment are summarised in Table 5.10. 


Table 5.10       Sound Power Level of Quiet PME

PME

EPD QPME Reference(a)(b)

Sound Power Level (dB(A))

Hand-held percussive breaker

EPD-07425

103

Generator

EPD-08020

91

Dump truck, 5.5 tonne < gross vehicle weight ≤ 38 tonne

EPD/PME/38

105

Excavator, mini-robot mounted

EPD/PME/13

94

Crane, mobile

EPD-07994

101

Note:

(a)      “Sound power levels of other commonly used PME” prepared by the Noise Control Authority  (http://www.epd.gov.hk/epd/english/application_for_licences/guidance/files/OtherSWLe.pdf)

(b)    Quality powered mechanical equipment (https://www.epd.gov.hk/cgi-bin/npg/qpme/search_gen.pl?lang=eng&st=sim&valid=Y)

            Adoption of Movable Noise Barriers

 

5.8.4         The use of noise barriers will be an effective means to mitigate the noise impact arising from the construction works, particularly for low-rise NSRs.  With reference to EIAO Guidance Note No. 9/2010 Preparation of Construction Noise Assessment Under the Environmental Impact Assessment Ordinance (EIAO GN No. 9/2010), the use of movable barrier for certain PME could generally provide a 5 dB(A) reduction for movable PME and 10 dB(A) for stationary PME.  The schematic configuration of movable noise barrier is presented in Annex 5C-4.

            Use of Noise Insulating Sheet

 

5.8.5         Noise insulating sheet would be adopted for PME such as drill rig (Annex 5C-5).  The noise insulating sheet should be deployed such that there would be no opening or gaps on the joints.  With reference to the approved EIA Report for West Island Line (WIL) (Register No.: AEIAR-126/2008 approved on 23 Dec 2008) and MTRC Contract C4420 Tsim Sha Tsui Modification Noise Assessment Report for VEP (July 2003), a reduction of over 10 dB(A) could be achieved with the use of the noise insulating sheet.  For a conservative assessment, a noise reduction of 10 dB(A) for the PME with deployment of noise insulating sheet was assumed in this assessment. 

            Adoption of Fixed Temporary Noise Barriers

 

5.8.6         In view of the close proximity between NSRs and the works areas for construction of DWFI system, fixed temporary noise barriers will be deployed at the working section as far as practicable.  Fixed temporary noise barriers of 3m in height with skid footing should be used and located within a few metres of stationary plant and mobile plant such that the line of sight to the NSR is blocked by the barriers.  The length of the barrier should be at least five times greater than its height. The noise barrier material should have a sufficient surface density of at least 7 kg/m2 and have no openings or gaps. Reference has been made to EIAO GN No. 9/2010; it is anticipated that the major noise source of movable PMEs, such as breaker, water pump, concrete lorry mixer and excavator, will be located within the nullah at a level lower than the top of the proposed fixed temporary noise barrier, and therefore these barriers could produce at least a 5 dB(A) noise reduction.  A sample sectional drawing showing the location of proposed temporary noise barrier and NSRs located along both sides of the nullah are shown in Annex 5C-6.

Scheduling of PME / Construction Activities

 

5.8.7         The construction activities will be planned and carried out in sequence rather than simultaneously at each location. Instead of being operated simultaneously, the PMEs would be grouped (see Annex 5C-7) and only one group of PME would be operated at any one time for each construction activity for reducing the construction noise impact.

 

5.8.8         It is considered practical to specify the quiet PME and noise mitigation measures described in Section 5.8.3 in the contract document to mitigate the construction noise impact.

 

5.8.9         With the implementation of the use of quiet PME and movable noise barriers for various construction activities, the mitigated noise levels at the representative NSRs were calculated and the results are summarised in Table 5.11 with details of the calculations given in Annex 5C-7.  The results indicated that the predicted façade noise levels are in the range of 58 to 74 dB(A) and 51 to 70 dB(A) at residential NSRs and educational NSRs, respectively.

 

5.8.10     The maximum predicted construction noise level at NSR14 would be 70 dB(A). This comply with the noise criteria of 70dB(A) during normal school days but exceed the criteria of 65 dB(A) during examination period. However, this potential exceedance can be avoided with special arrangement below. For NSR18, the maximum predicted construction noise level would be 65 dB(A) and meet the noise criteria during examination period. However, in order to minimize the potential cumulative impact with concurrent projects discussed in Section 5.9, the following special arrangement during examination period is recommended:

Special arrangement during examination period

·                     The contractor could liaise with the school management about the arrangements during examination weeks.

·                     PMEs shall not be used at the closest works areas (i.e. Section B1 for NSR14 and Section A3 for NSR18) during the examination period.

 

5.8.11     With the above arrangements in place, the predicted maximum construction noise level at both NSR 14 and NSR 18 would be 55 dB(A).  As there would be no exceedance of the noise criterion during examination period, no unacceptable impact is expected at the NSRs at that particular period.

 

5.8.12     Table 5.11 shows that the predicted construction noise levels at all NSRs comply with the noise criteria during the daytime period, therefore, no unacceptable noise impact is expected to arise from the construction activities to be carried out within the works areas.

 

Table 5.11        Predicted Construction Noise Levels (With Mitigation Measures)

NSR No.

Description

Predicted Noise Level, dB(A)

Noise Criteria, Leq, 30min, dB(A)

NSR01

Tung Tau Wai San Tsuen

63

75

NSR02

Shan Pui Chung Hau Tsuen

67

75

NSR03

Twin Regency

74

75

NSR04

Yuk Yat Garden

60

75

NSR05

Wang Fu Court

60

75

NSR06

Yeung Uk San Tsuen

60

75

NSR07

Yuen Long Long Ping Estate Wai Chow School

57

70/65 (a)

NSR08

The Spectra

61

75

NSR09

Tai Kiu Tsuen

71

75

NSR10

Fuk Yip Building

73

75

NSR11

Yuen Fat House

74

75

NSR12

Healey Building

68

75

NSR13

Wah Shing Mansion

70

75

NSR14

CCC Chun Kwong Primary School

70 (normal school days) / 55 (examination period)

70/65 (a)(b)

NSR15

Tse King House

65

75

NSR16

On Ning Building

67

75

NSR17

Ho Wang Building

74

75

NSR18

Caritas Yuen Long Chan Chun Ha Secondary School

65 (normal school days) / 55 (examination period)

70/65 (a)

NSR19

Sun Fai Court

74

75

NSR20

Ma Tin Tsuen - Kung Um Road

72

75

NSR21

Yuen Long Villa

73

75

NSR22

Lung Tin Tsuen

58

75

NSR23

Wang Chau Lam Uk Tsuen

60

75

NSR24

Wang Chau Tung Tau Wai

59

75

NSR25

Hong Kong School of Motoring - Yuen Long Road Safety Centre

51

70/65 (a)

R1

Sol City (Planned)

70

75

Notes:

(a)                 70/65 denotes noise criteria during normal school days / examination period, respectively.

(b)                With the special construction arrangements specified in Section 5.8.10 in place, no exceedance of the noise criterion during examination period is anticipated

            Operation Phase

 

5.8.13     While no unacceptable noise impact is expected due to the operation of fixed plant items, it is still recommended that the following measures be implemented as far as practicable to minimise the potential impact:

·                     Quieter plant should be chosen as far as practical;

·                     Include noise levels specification when ordering new plant items;

·                     All openings, including louvres for ventilation and machine room doors should be oriented away from the NSRs as far as practicable;

·                     Silencers, acoustic louvres or acoustic doors should be used where necessary; and

·                     Develop and implement a regularly scheduled plant maintenance programme so that plant items are properly operated and serviced.  The programme should be implemented by properly trained personnel.

 

5.8.14     Testing and commissioning of the proposed DWF pumping station would be carried out prior to operation. Noise monitoring would be carried out by the Contractor to ensure fixed noise sources impact would comply with the relevant noise standards.

 

Assessment of Side Effects and Constraints

 

5.8.15     In accordance with the requirements stated in Clause 6 in Appendix B of the EIA Study Brief, no side effects and constraints due to the inclusion of the recommended mitigation measures have been identified.

 

5.9              Cumulative Impacts

 

Construction Phase

 

5.9.1         There are three concurrent projects potentially causing cumulative noise impacts. They are:

·           Yuen Long Barrage Scheme;

·           Elevated Pedestrian Corridor in Yuen Long Town Connecting with Long Ping Station; and

·           Housing Sites in Yuen Long South.

 

Yuen Long Barrage Scheme (YLBS)

5.9.2         With reference to the Project Profile of YLBS, the only works within 300m area from the most of the NSRs, except NSR 25, identified for the Project (Improvement of YLTN) is nullah revitalization. With consultation from DSD, the nullah revitalization will be carried out by Barrage Scheme after the construction works of Improvement of YLTN. For NSR 25, the maximum predicted mitigated construction noise levels from the YLTN Project is 51 dB(A). No unacceptable cumulative noise impact is anticipated.

 

Housing Sites in Yuen Long South

5.9.3         According to the EIA report of the housing development, no unacceptable noise impact is anticipated by good site practices, use of noise barrier, “quiet” plant and working method. There is no overlap of the project boundary of the housing development and YLTN Project. The NSR 22 “Lung Tin Tsuen” would be the closest NSR to the housing development and the maximum predicted mitigated noise level from the YLTN Project is 58 dB(A). No unacceptable cumulative noise impact is anticipated. 

 

Elevated Pedestrian Corridor in Yuen Long Town Connecting with Long Ping Station (EPC)

5.9.4         With consultation from HyD, the project is tentatively scheduled to commence in first quarter of 2020 for completion in first quarter of 2025. Compared with the implementation programme in the EIA report, the expected commencement date was first quarter of 2018. In view of it, the predicted construction noise levels (with mitigation) in Appendix 5.8 of the EIA report (AEIAR-200/2016) is applied with adjustment of 2-year forward. The predicted cumulative construction noise levels are summarized in Table 5.12. The detailed calculation is presented in Annex 5C-8.

 

Table 5.12       Predicted Cumulative Construction Noise Levels

NSR

Description

Max. Predicted Cumulative CNL, dB(A)

Noise Criteria

Leq, 30min, dB(A)

Exceedance

NSR09

Tai Kiu Tsuen

73

75

No

NSR12

Healey Building

74

75

No

NSR14

CCC Chun Kwong Primary School

70 (normal school days) / 68 (examination period)

70/65 (a)

Yes (b)

NSR15

Tse King House

72

75

No

NSR16

On Ning Building

69

75

No

NSR17

Ho Wang Building

74

75

No

NSR18

Caritas Yuen Long Chan Chun Ha Secondary School

66 (normal school days) / 58 (examination period)

70/65 (a)

No

Notes:

(a)                70/65 denotes noise criteria during normal school days / examination period, respectively.

(b)                The construction noise level during examination period due to the current project alone is only 55dB(A) which is 10 dB(A) below the criteria of 65dB(A).  The exceedance of cumulative noise is due to the EPC project only.  The EIA report of the EPC project also recommended special construction arrangements to avoid this potential exceedance.

 

5.9.5         The predicted cumulative CNL at NSRs will comply with noise criteria except for NSR14. The maximum predicted cumulative CNL at NSR14 is 68 dB(A) during the examination period which exceeds the noise criteria of 65 dB(A). According to the approved EIA report of the EPC project (AEIAR-200/2016), the predicted CNLs at NSR14 due to the EPC project is 68 dB(A) during examination period which already exceeds the criteria of 65 dB(A). As the predicted mitigated CNL at NSR14 due to the YLTN Project is 55 dB(A) during examination period which is 10 dB(A) below the criteria of 65 dB(A), the potential contribution from the YLTN Project to the cumulative impacts to the NSR is considered as negligible. According to the approved EIA Report of the EPC project, the potential exceedance would be avoided by special construction arrangement during examination periods. As such, no unacceptable cumulative noise impact is anticipated.

 

Operation Phase

 

5.9.6         There are existing DSD pumping facilities located in approximately 90m to the north-east of the proposed DWF pumping station.  Cumulative noise impact from the existing pumping facilities and the proposed DWF pumping station has been taken into account in this assessment.  Reference has been made to the approved Environmental Review Report for application of VEP for Yuen Long Kau Hui No. 2 Sewage Pumping Station with Environmental Permit (VEP-455/2014) issued by EPD in December 2014 for the noise data of the existing pumping facilities.  A figure showing the locations of the existing pump facilities, including Yuen Long LFPS, Yuen Long Kau Hui Floodwater Pumping Station, Yuen Long Kau Hui Sewage Pumping Station and Yuen Long Kau Hui No. 2 Sewage Pumping Station, is given in Annex 5C-9. It is noted from the Environmental Review Report that the LFPS and the Kau Hui Floodwater Pumping Station will not be operated simultaneously. The pumping station with higher noise level and closer to the respective NSRs (i.e. LFPS) has been included in the cumulative impact assessment.

 

5.9.7         The cumulative noise level of the proposed pumping station together with the existing pumping stations shall comply with the noise criteria under the NCO. The cumulative noise levels with the operation of the existing pumping stations are summarised in Table 5.13.  The predicted cumulative noise levels at all the representative NSRs comply with the day-time and night-time noise criteria as shown in Section 5.2.11.  Details of the calculation are given in Annex 5C-10.

 

Table 5.13       Predicted Cumulative Fixed Plant Noise Levels

NSR

Description

Predicted Cumulative Fixed Plant Noise Level, dB(A)

ASR

Applicable Noise Limit, dB(A)

Exceedance

NSR 1

Tung Tau Wai San Tsuen

33

B

55

No exceedance

NSR 2

Shan Pui Chung Hau Tsuen

39

B

55

No exceedance

NSR 3

Twin Regency

46

B

55

No exceedance

NSR 4

Yuk Yat Garden

27

A

50

No exceedance

NSR 5

Wang Fu Court

28

A

50

No exceedance

NSR 23

Wang Chau Lam Uk Tsuen

32

A

50

No exceedance

NSR24

Wang Chau Tung Tau Wai

31

B

55

No exceedance


5.10          Residual Impacts

 

Construction Phase

 

5.10.1     With the implementation of practical noise mitigation measures, including the use of quiet PME, movable noise barriers, noise insulation sheet and scheduling of construction activities, it is predicted that there is no exceedance of the daytime construction noise criteria at all NSRs.  Therefore, unacceptable residual impact is not anticipated.

 

Operation Phase

 

5.10.2     Both the predicted noise levels due to the operation of the proposed DWF pumping station and the cumulative noise levels with the operation of the existing pumping stations at all the representative NSRs comply with the day-time and night-time noise criteria.  Thus, unacceptable residual impacts are not anticipated from the operation of the Project provided that the appropriate contract specifications and noise abatement measures as mentioned in Section 5.8 are incorporated in the Detailed Design.

 

5.11          Monitoring and Audit Requirement

            Construction Phase

 

5.11.1     The recommended mitigation measures, monitoring procedures and locations are presented in detail in the Environmental Monitoring and Audit (EM&A) Manual.  This will facilitate the contractor to have early warning and undertake the necessary actions to reduce noise emissions at specific areas.  The effectiveness of on-site control measures could also be evaluated through the regular site audits.  All the recommended mitigation measures should be incorporated into the EM&A programme for implementation during construction.

            Operation Phase

 

5.11.2     Noise monitoring for the operation of DWF pumping station is considered unnecessary during the operation phase. 

 

5.12          Conclusion

 

Construction Phase

 

5.12.1     A construction noise assessment has been undertaken to predict the noise levels at the representative NSRs due to the construction of the Project.  Practicable mitigation measures, including good construction site practices, use of quiet construction plant, movable noise barriers, noise insulation sheet and scheduling of construction activities, have been recommended.  With the implementation of the recommended mitigation measures, the predicted construction noise levels at all NSRs comply with the noise criteria during the daytime period.  Therefore, no unacceptable noise impact is expected to arise from the construction activities.  Also, no unacceptable cumulative impact or residual impact is anticipated.  Regular noise monitoring at NSRs as part of the EM&A programme during the construction stage is recommended. 

 

Operation Phase

 

5.12.2     Potential noise impact from the operation of the proposed DWF pumping station has been assessed.  The predicted fixed plant noise levels at the representative NSRs due to the operation of the proposed DWF pumping station and the cumulative noise levels with the operation of the existing pumping stations comply with the day-time and night-time noise criteria.  No unacceptable residual impact is anticipated.  Attenuation measures, if required, will be provided to the fixed plant items for achieving the compliance of EIAO-TM noise criteria during the detailed design stage.

 

5.13          References

 

1)      DSD (2014) – Environmental Review Report for application of Variation of Environmental Permit (VEP) for “Yuen Long Kau Hui No. 2 Sewage Pumping Station” (VEP-455/2014).



([1])     “Sound power levels of other commonly used PME” prepared by the Noise Control Authority (http://www.epd.gov.hk/epd/sites/default/files/epd/english/application_for_licences/guidance/files/OtherSWLe.pdf)